Boiler Tuneup                                                                                      99






























                Figure 9.19—Flame is narrow and does not fill the   Figure 9.20—Flame pattern with intermittent oil
                throat. Possible thin stream of oil present in the mid-  slugs coming out of the tip.
                dle of the flame.
                                                                    Problem:
                Problem:                                            •    Atomizer problem, tip partially plugged, tip
                •    Low  oil  pressure  delta-p  or  return  oil  line   worn or other burner tip problem.
                     plugged.
                •    Air register open too far.






























                Figure 9.21—Flame blow off. May be continuous or    Figure 9.22—Flame clears throat, but rolls back, im-
                pulsating on and off the tip.                       pinges and rolls up the furnace wall.

                Problem:                                            Problem:
                •    Air register open too far.                     •    Air register closed too far.
                •    Oil gun positioned too far in toward the furnace.