Page 281 - Boiler plant and distribution system optimization manual
P. 281

266                                                 Boiler Plant and Distribution System Optimization Manual


                     $2000 in steam each day—even though $500       bottom of the reservoir is a dirt pocket and valve
                     or more is spent daily on steam trap mainte-   to collect larger particles of scale and dirt in the
                     nance.”                                        system. It has a blowoff valve for clean-out.
                                                   Industry Week         The  condensate  flows  from  the  collection
                                                   April 16, 1984   point through a strainer and trap to the conden-
                                                                    sate system. The station is configured with inlet
                                                                    and outlet valves to isolate the trap if repairs are
                                                                    needed.
                     This review of some of the most prestigious         The test connection can be opened, coordi-
                and informed publications on efficient plant man-   nated with the closing of the trap outlet valve to
                agement are all of one voice. There is tremendous   see  what  is  coming  through  the  trap,  steam  or
                potential to waste energy in steam systems, also    condensate. This  is one  of the  best ways to test
                there is the same level of opportunity to correct   trap performance.
                the situation.                                           The “Y” strainer can be cleaned out by open-
                                                                    ing the blowoff valve.
                                                                         The  bypass  line  (not  shown)  enables  plant
                STEAM TRAP SELECTION SIzING                         personnel to bypass the entire steam trap station
                AND INSTALLATION                                    if necessary. Bypass valves are usually opened
                                                                    when there is a suspected problem with a trap or
                Steam Trap Piping                                   to assist with drainage during cold startup. By-
                     In most plants, the removal of condensate      passing  a steam  trap may  also  be necessary to
                and air from steam systems is accomplished          deal  with  a  waterlogging  problem  caused  by  a
                through steam trap stations. Figure 14.21 shows     trap malfunction.
                the piping configuration for a steam trap station.       With the bypass open, steam will be wasted
                                                                    and the efficiency of the plant reduced. In some
                                                                    cases a trap is installed in the bypass line. Then,
                                                                    if the main trap fails, the bypass trap can be put
                                                                    into  service  and  the  problem  of  blowing  steam
                                                                    through the bypass is eliminated.


                                                                    Selecting the Type of Trap
                                                                         Properly selected, sized and installed traps
                                                                    are the best guarantee for efficient operation, long
                                                                    service life and minimum downtime.
                                                                         The major considerations in selecting the
                                                                    type of steam trap are:


                                                                    A.  Type of service
                                                                         •  Continuous  or  intermittent  removal  of
                     Figure 14.21—A typical steam trap station.              condensate
                                                                         •  Temperature of the condensate and sys-
                     The first part of the steam trap station is a           tem pressure
                reservoir that connects to the lowest point of the       •  Range of load on the trap
                steam line or process equipment.  The reservoir          •  Rate of change of the load
                is  sized  to  collect  the  large  quantity  of  conden-
                sate formed during the warmup phase when the        B.   Operational
                system is brought up from the cold state. At the         •  Normal steam loss during operation
   276   277   278   279   280   281   282   283   284   285   286