Page 43 - Buried Pipe Design
P. 43

External Loads  21









                                P
                               r


           H  B c

















                        B d
                        B c
         Figure 2.6 Curves for transition-width ratio. (Reprinted, by permission,
         from Spangler and Handy, Soil Engineering, 4th ed., Harper & Row, 1982.)



           Example Problem 2.2 What is the transition width for a 12-in pipe buried
           6 ft deep?
                               H      6 ft   12 in
                                                    6
                               B     12 in   1 ft
                                C
           From Fig. 2.6,
                                      B d
                                           2.35
                                      B c
                                     r sd p   0.5

                                      B d
                      B d (transition)      B c   2.35 (1 ft)   2.35 ft
                                      B c
         Tunnel construction. Marston’s theory may be used to determine soil
         loads on pipes that are in tunnels or that are jacked into place through
   38   39   40   41   42   43   44   45   46   47   48