Page 69 - Chemical Process Equipment - Selection and Design
P. 69

3.1.  FEEDBACK CONTROL  41

            3.  Derivative, in which the corrective action is proportional to the   of  cooling  water  is  fixed  accordingly.  Suppose  the  heat  load  is
              rate at which the error is being generated.      doubled suddenly because of  an increase in the reactor contents. At
                                                               steady state the valve will remain 50% open so that the water flow
            The  relation  between  the  change  in  output  rn - rn,  and  input  e   rate also will remain as before.  Because of  the greater rate of  heat
            signals accordingly is represented by              evolution, however, the  temperature  will rise  to  a higher but  still
                                                               steady value. On the other hand, the corrective action of  an integral
               rn - rn, = K, (e + :; le dt -k                  controller  depends  on  displacement of  the  temperature  from  the
                                      dt
                                                               original  set  point,  so  that  this  mode  of  control  will  restore  the
                                                               original temperature.
            Just  how  these  modes  of  action  are  achieved  in  relatively   The constants Kp, K,,  and Kd are  settings of  the instrument.
            inexpensive pneumatic or electrical devices is explained in books on   When  the  controller  is  hooked  up  to  the  process,  the  settings
            control  instruments,  for  example,  that  of  Considine  (Process   appropriate  to  a  desired quality of  control  depend  on the  inertia
            Instruments and Controls Handbook, Sec. 17, 1974). The low prices   (capacitance) and various response times of  the  system, and they
            and  considerable  flexibility  of  PID  controllers  make  them  the   can be determined by field tests. The method of Ziegler and Nichols
            dominant  types in  use,  and  have  discouraged the  development of   used in Example 3.1 is based on step response of  a damped system
            possibly superior types, particularly as one-shot deals which would   and  provides  at  least  approximate  values  of  instrument  settings
            be the usual case in process plants. Any desired mode of  action can   which can be further fine-tuned in the field.
            be simulated by  a computer, but at a price.          The kinds of  controllers suitable for the common variables may
               A  capsule  summary  of  the  merits  of  the  three  kinds  of   be stated briefly:
            corrective action can be made. The proportional action is rapid but
            has a permanent  offset that increases a5 the action speeds up.  The   Variable   Controller
            addition of  integral action reduces or  entirely eliminates the offset
            but has a more sluggish response. The further addition of  derivative   Flow and liquid pressure   PI
            action speeds up  the  eorrection.  The  action of  a three-mode PID   Gas pressure   P
                                                                         Liquid level
            controller can be  made rapid and without offset. These effects are   Temperature   P or PI
                                                                                             PID
            illustrated in Figure 3.3 for a process subjected to a unit step upset,   Composition   P, PI,  PID
            in this case a change in the pressure of  the control air. The ordinate
            is the ratio of  the displacements of  the response and upset from the   Derivative control is  sensitive to noise that  is made up of  random
            set point.                                         higher  frequency perturbations,  such  as  spiashing and  turbulence
               The  reason  for  a  permanent  offset with  a  proportional  con-   generated by inflow in the case of  liquid level control in a vessel, so
            troller  can  be  explained with  an  example.  Suppose the  tempera-   that  it  is  not  satisfactory  in  such  situations.  The  variety  of
            ture  of  a  reactor  is  being  controlled  with  a  pneumatic  system.   composition controllers arises because of  the variety of  composition
            At  the  set  point,  say  the  valve  is  50%  open  and  the  flow  rate   analyzers or detectors.
                                                                   Many  corrective  actions  ultimately  adjust  a  flow  rate,  for
                                                               instance,  temperature  control  by  adjusting  the  flow  of  a  heat
                                                               transfer  medium  or pressure  by  regulating the  flow  of  an  effluent
                                                               stream. A  control unit thus  consists of  a detector,  for example, a
                                                               thermocouple,  a  transmitter,  the  control  instrument  itself,  and  a
                                                               control  valve.  The  natures,  sensitivities,  response  speeds,  and
                                                               locations of  these  devices, together with the  inertia   capacity of
                                                               the  process equipment,  comprise the body  of  what  is  to be taken
                                                               into  account when  designing the  control  system. In  the  following
                                                               pages  will  be  described only  general  characteristics of  the  major
                                                               kinds  of  control  systems  that  are  being  used  in  process  plants.
                                                               Details and criteria for choice between possible alternates must be
                                                               sought elsewhere. The practical aspects of  this subject are treated,
                                                               for example, in the References at the end of  this chapter.

                                                               SYMBOLS
                                                               On working flowsheets the  detectors,  transmitters,  and controllers
                                                               are identified individually by  appropriate letters and serial numbers
                                                               in circles. Control valves are identified by the letters CV- followed
                                                               by  a serial number. When the intent is to show only in general the
                                                               kind of  control system, no special symbol is used for detectors, but
                                                               simply  a point of  contact of  the signal line with the equipment or
                                                               process line.  Transmitters  are  devices that  convert  the  measured
                                                               variable  into  air  pressure  for  pneumatic  controllers  or  units
                                                               appropriate  for  electrical  controllers.  Temperature,  for  instance,
                                                               may  be  detected  with  thermocouples  or  electrical  resistance  or
                                                               height of  a liquid column or radiant flux, etc., but the controller can
                                                                accept  only pneumatic or  electrical signals depending on  its type.
                                   Time, sec                    When the nature of  the transmitter is clear, it may be represented
            Figure  3.3.  Response  of  various  modes  of  control  to  step  input   by an encircled cross or left out entirely. For clarity, the flowsheet
            (Eckimun, Automatic Psocess Control, Wiley, New York, 1958).   can include only the most essential information. In an actual design
   64   65   66   67   68   69   70   71   72   73   74