Page 350 - Compression Machinery for Oil and Gas
P. 350

Drivers Chapter  7 335



                                 Stator magnetic field rotation
                                                  Dotted line -
                                        C
                                                  unstable
                             N                              S
                                        B         operation
                                  h
                                         A
                            m
                                 d
                       Magnetic
                       flux in
                                                              Electrical
                       air-gap                                degrees
                              d
                                            90°
                               0°                       180°
                                  32°
                                    S'
                                 S                     N
                                           Rotor
             FIG. 7.21 Synchronous motor operation in synchronism: at full load (example 32 degrees) and at
             no load (0 degree).

                                               r  ffiffiffiffiffiffiffiffiffiffiffiffi
                                       35;200    P r  f
                                   f n ¼            2                   (7.7)
                                         n       WK
             where f n is the undamped natural frequency in cycles/min, n is the synchronous
             speed in rpm, P r is the synchronizing torque coefficient, this is the stiffness of
             the electrical field applying torque to the rotor to restore it to the neutral position
             in units of KW/rad (see NEMA MG1 21.36.2), and f is the electrical line fre-
                            2
                                                   2
             quency in Hz, WK is the inertia in units lbs-ft .
                The electrical natural frequency obviously must be separate from the run-
             ning speed in order for the current pulsation to be below 66%. Usually, it is
             between 0.5 and 0.75 times the running speed. Also referring to the NEMA
             MG1 21.38, there is a term called the compressor factor C.
                                                 2
                                       0:746 WK  n   4
                                    C ¼                                 (7.8)
                                         P r  f  108
                Therefore, the term compressor factor (C) gives a dimensionless measure of
             the inertia in the motor and driven system. At C ¼9.24, the system is in elec-
             trical resonance and the natural frequency is proportional to 1/C1/2. Generally
             for the multiple throw machine such as a six-throw, satisfactory current pulsa-
             tion will normally be achieved at C ¼20 (f n ¼0.68 running speed) and for a
             two-throw at C ¼30 or greater (f n ¼0.55 running speed). It is typically
             acceptable to have a motor with minimum C ¼20 for a two-throw and
             C ¼15 for four-throw or more. Any additional inertia required will be in the
             compressor or can be added to the compressor flywheel. The current pulsation
             for both induction and synchronous motors should always be checked during the
             engineering phase by the motor manufacturer using the full load and part load
   345   346   347   348   349   350   351   352   353   354   355