Page 164 - Defrosting for Air Source Heat Pump
P. 164

158                                         Defrosting for Air Source Heat Pump































         Fig. 6.4 Measured tube surface temperatures at the exits of the three refrigerant circuits on
         heating mode before frosting growth in Case 2.


         6.2.2 Results and analysis
         Fig. 6.5 presents 12 photographs showing the airside surface conditions of the outdoor
         coil during frosting in the two cases. As observed from Fig. 6.5A1 and B1, the surface
         conditions at the start of defrosting for each circuit in the two cases were virtually the
         same, except that there was less frost on the upside of Circuit 3 in Case 1 than the
         downside, which agreed well with the trends of measured tube surface temperatures
         on heating mode before frosting growth, as shown in Figs. 6.3 and 6.4. From
         Fig. 6.5A1–A6, it can be seen that the frost accumulated on the airside of the outdoor
         coil increased with time. However, the frost accumulations were not even for the three
         circuits. It is obvious that the frost accumulated on Circuit 3 keeps fewer than that on
         the other two circuits. As seen from Fig. 6.5B1–B6,the frost accumulated evenly on
         the three circuits with time.
            As shown in Table 6.1, the results of two experimental cases are listed. The total
         mass of frost accumulated is 1000 g in Case 1 and 1001 g in Case 2, which are nearly
         the same. In Case 1, the masses of frost accumulated on each circuit’s surface are
         355 g for Circuit 1, 367 g for Circuit 2, and 278 g for Circuit 3, respectively. The mass
         order of frost accumulation is Circuit 1   Circuit 2 > Circuit 3, which well agrees
         with the temperature order of T Circuit 1   T Circuit 2 < T Circuit 3 , as shown in Fig. 6.3.
         This is because the opening degrees of the stop valves are kept constant during frosting
         in Case 1. The FEC is calculated at about 75.7%. However, in Case 2, the masses of
         frost accumulated on each circuit’s surface are orderly at 346 g, 313 g, and 342 g,
   159   160   161   162   163   164   165   166   167   168   169