Page 169 - Defrosting for Air Source Heat Pump
P. 169

Frosting evenness coefficient                                     163


                        0
                                        Fin in Case 1     Fin in Case 2
                       –2

                       –4
                     Fin surface temperature ( o C)  –10
                       –6

                       –8



                      –12
                      –14

                      –16
                           0    500  1000  1500  2000  2500  3000  3500  4000
                                             Time (s)

           Fig. 6.12 Measured average fin surface temperatures at the center of the three circuits during
           frosting in the two cases.


                      4.8
                                          Case 1     Case 2

                      4.4

                      4.0
                     COP (/)  3.6




                      3.2


                      2.8
                           0    500  1000  1500  2000  2500  3000  3500  4000
                                             Time (s)
           Fig. 6.13 COP variation of the ASHP unit during frosting in the two cases.


           pressure drop increased. This resulted from the heat transfer between the ambient air
           and the refrigerant becoming hard as frost accumulated on the surface of the outdoor
           coil. And this agrees well with the temperature decrease of the refrigerant, as shown in
           Figs. 6.6 and Figs. 6.7. Due to the higher FEC in Case 2 than that in Case 1, the trends
           of increasing and decreasing in Case 1 were bigger than those in Case 2.
   164   165   166   167   168   169   170   171   172   173   174