Page 165 - Defrosting for Air Source Heat Pump
P. 165

Frosting evenness coefficient                                     159
























           Fig. 6.5 Airside surface conditions of the outdoor coil during frosting in two cases.


            Table 6.1 Results of two experimental cases
            Item   Parameter                 Case 1              Case 2
            1      Frost accumulation on Circuit 1  355 g        342 g
            2      Frost accumulation on Circuit 2  367 g        313 g
            3      Frost accumulation on Circuit 3  278 g        346 g
            4      Total mass of melted frost  1000 g            1001 g
            5      FEC                       75.7%               90.5%
            6      Results shown in          Figs. 6.5, 6.6, 6.8–6.13  Figs. 6.5,
                                                                 6.7–6.13


           respectively, from Circuit 1 to 3. The mass order of frost accumulation is
           Circuit 1   Circuit 2   Circuit 3, which does not agree with the temperature order of
           T Circuit 1   T Circuit 2 < T Circuit 3 ,as shownin Fig. 6.4. This is because the opening degrees
           of the stop valves are not constant during frosting in Case 2, but randomly adjusted to
           makethetubesurfacetemperatureattheexitofeachcircuitthesame.Therefore,although
           the temperature of Circuit 3 in Fig. 9 is the highest from 300 s to 2800 s on heating
           mode before frosting growth, it is no matter with the frost accumulation at the end of
           the frosting process. Finally, the FEC is calculated at about 90.5%, which is about
           14.8% higher than that in Case 1.
              Moreover, the measured operating performances of the experimental ASHP unit
           during frosting, corresponding to the two experimental cases, are presented in
           Figs. 6.6–6.12 . Figs. 6.6 and 6.7 present the measured tube surface temperatures
           at the exits of the three refrigerant circuits. Figs. 6.8 and 6.9 present the Gauss fit
           of the measured refrigerant volume flow rate and the measured refrigerant pressure
           drop across the outdoor coil in the two cases. Figs. 6.10–6.12 show the measured
           air temperature difference between the indoor coil inlet and the outlet, the tube surface
   160   161   162   163   164   165   166   167   168   169   170