Page 173 - Defrosting for Air Source Heat Pump
P. 173

Frosting evenness coefficient                                     167

           installed multicircuit outdoor coil when its defrosting operation starts at different
           FECs is very meaningful and fundamental.
              As shown in Table 6.2, the results of the three experimental cases are listed in
           detail. The total mass of frost accumulated was weighed at 878 g in Case 1, 894 g
           in Case 2, and 881 g in Case 3. The three values are nearly the same, with the biggest
           difference of 16 g, or just 1.8% (<10%), which makes the comparative study and
           experimental results meaningful. In addition, in Case 1, the masses of frost accumu-
           lated on each circuit’s surface were weighed at 301 g for Circuit 1, 316 g for Circuit 2,
           and 261 g for Circuit 3, respectively. The FEC was calculated at about 82.6%. In Case
           2, the frost accumulations from Circuit 1 to Circuit 3 were weighed at 280 g, 309 g,
           and 305 g, respectively. The FEC was calculated at about 90.6%, which was about
           8.0% higher than that in Case 1. As to Case 3, from Circuit 1 to Circuit 3, the frost
           accumulations were weighed at 288 g, 298 g, and 295 g, respectively. The FEC in
           Case 3 was calculated at about 96.6%, or 14.0% higher than that in Case 1.
              Moreover, the measured operating performances of the experimental ASHP unit
           during defrosting, corresponding to the three experimental cases, are presented in
           Figs. 6.15–6.22. Figs. 6.15–6.17 present the measured tube surface temperatures at
           the exits of the three refrigerant circuits during defrosting, and Figs. 6.18–6.20 show
           the measured fin surface temperature at the center of the three refrigerant circuits dur-
           ing defrosting. In all these figures, for their time (horizontal) axis, 80 s is the chosen
           starting time in order to clearly show the temperature rise during defrosting. Fig. 6.21
           shows the measured temperature of the surrounding air and the measured tempera-
           ture of the melted frost collected in Cylinder C during defrosting in the three cases.



                       32
                                    Circuit 1     Circuit 2     Circuit 3
                       28
                                                   T  > T  > T 3
                                                    2
                                                       1
                       24
                      Temperature of tube surface ( o C)  16 8  T  > T  > T  1
                       20

                                       2
                                          3
                       12


                        4
                                 126 s
                                                         202 s
                                               144 s     205 s
                        0
                         80    100   120   140   160   180    200   220
                                             Time (s)

           Fig. 6.15 Measured tube surface temperatures at the exits of the three refrigerant circuits during
           defrosting in Case 1.
   168   169   170   171   172   173   174   175   176   177   178