Page 176 - Defrosting for Air Source Heat Pump
P. 176

170                                         Defrosting for Air Source Heat Pump


                     32
                     28
                                T  > T  > T
                                 1   2  3                 T  > T  > T
                                                           1  3  2
                     24      Fin in Circuit 1
                    Temperature of fin surface ( o C)  16 8   Fin in Circuit 2
                     20
                             Fin in Circuit 3


                     12



                      4
                                          185 s        196 s
                      0

                       80  100  120  140  160  180  200  220  240  260
                                           Time (s)

         Fig. 6.20 Measured fin surface temperature at the center of three refrigerant circuits during
         defrosting in Case 3.







                     1.8
                                     Case 1     Case 2     Case 3
                    Measured refrigerant volumetric flow rate (L/M)  1.2  Fluctuating   R Case 3  > R  Case 2  > R Case 1
                     1.6
                     1.4



                     1.0
                     0.8
                     0.6

                     0.4
                     0.2
                                                             180 s
                     0.0                      174 s          180 s
                        0     40     80     120    160     200    240
                                           Time (s)

         Fig. 6.21 Measured refrigerant volumetric flow rate during defrosting in the three cases.
   171   172   173   174   175   176   177   178   179   180   181