Page 175 - Defrosting for Air Source Heat Pump
P. 175

Frosting evenness coefficient                                     169


                       32
                                 Fin in Circuit 1
                       28        Fin in Circuit 2
                                 Fin in Circuit 3
                                             T  > T  > T
                       24                     3  1   2
                      Temperature of fin surface ( o C)  16 8
                       20




                       12



                        4
                                              125 s  220 s      235 s
                        0

                         80  100  120  140  160  180  200  220  240  260
                                             Time (s)

           Fig. 6.18 Measured fin surface temperature at the center of three refrigerant circuits during
           defrosting in Case 1.







                       32
                                 Fin in Circuit 1
                       28        Fin in Circuit 2
                                 Fin in Circuit 3    T  > T  > T
                                                   1  2  3
                       24
                      Temperature of fin surface ( o C)  16  T  > T  > T 1
                       20



                       12

                                    3
                                        2
                        8
                        4
                               125 s
                                             150 s   185 s    218 s
                        0
                         80  100  120  140  160  180  200  220  240  260
                                             Time (s)

           Fig. 6.19 Measured fin surface temperature at the center of three refrigerant circuits during
           defrosting in Case 2.
   170   171   172   173   174   175   176   177   178   179   180