Page 177 - Defrosting for Air Source Heat Pump
P. 177

Frosting evenness coefficient                                     171


                       2.8
                                       Case 1     Case 2     Case 3
                       2.4     T  Case 3  > T Case 2  > T Case 1  T Case 1  > T  Case 2  > T Case 3
                      Temperature of melted frost collected ( o C)  1.6  Temperature of surrounding air  melted frost collected
                       2.0




                       1.2

                                                         Temperature of
                       0.8
                       0.4

                       0.0           135 s  145 s      150 s    187 s
                          0    30   60   90   120   150  180  210   240
                                             Time (s)
           Fig. 6.22 Measured temperature of the surrounding air and measured temperature of the melted
           frost collected in Cylinder C during defrosting in the three cases.




           Finally, a variation of the measured refrigerant volumetric flow rate during defrosting
           in the three cases is shown in Fig. 6.22.
              Due to the negative effects of downward-flowing melted frost on defrosting
           performance, the temperature curves of the three circuits’ order should be at
           T 1 > T 2 > T 3 , the same as that shown in Fig. 3.13 in Chapter 3. However, as shown
           in Fig. 6.15, the temperatures were observed at T 2 > T 3 > T 1 from 126 s to 144 s, and
           at T 2 > T 1 > T 3 from 144 s to 205 s into defrosting. This contradictory phenomenon
           might owe to the fact that the FEC was calculated at just 82.5% in Case 1, which was
           less than that reported in Chapter 3, at a FEC higher than 90%. In addition, the same
           phenomenon came out in the other two cases, although the FECs were both calculated
           higher than 90%, at 90.6% in Case 2 and 96.6% in Case 3. In Case 2, as shown in
           Fig. 6.16, the temperature curves’ order kept at T 2 > T 1 > T 3 from 80 s to 148 s. After
           148 s, the order was changed to at T 1 > T 2 > T 3 . In Case 3, as shown in Fig. 6.17, the
           order was at T 2 > T 1 > T 3 from 80 s to 138 s, and then changed to at T 1 > T 2 > T 3
           from 138 s to 185 s. Therefore, an uneven refrigerant distribution for three circuits
           during defrosting might be another reason resulting in the temperature curves of three
           circuits order not at T 1 > T 2 > T 3 during defrosting. This also may be the reason why
           the temperature curve of Circuit 2 was always higher than the others in the three cases.
              Moreover, as shown in Figs. 6.15–6.17, the defrosting durations were 202 s in Case
           1, 196 s in Case 2, and 185 s in Case 3, respectively. It means the defrosting duration
           would be decreased when an RCD operation starts at a higher FEC. Therefore, the
           conclusion that the system defrosting performance could be improved by a higher
   172   173   174   175   176   177   178   179   180   181   182