Page 375 - Design of Reinforced Masonry Structures
P. 375

6.26                       CHAPTER SIX

         6.5.2 Wind Loads
         Provisions for determining design loads caused by wind are presented in Chap. 6 of ASCE
         7-05 [6.19]. These provisions, although different in some respects, bear striking philo-
         sophical resemblance to their counterpart in ASCE 7-98 Standard [6.21] and discussed in
         Ref. 6.20. It is noted that design provisions for wind loads in 2009 IBC [6.2] direct readers
         to ASCE 7-05 Standard [6.19]; the requirements contained in the latter and used in this
         chapter are discussed as follows.
           ASCE 7-05 Standard provides three methods for determining wind pressure on building
         structures: (1) simplified method, (2) analytical method, and (3) wind tunnel procedure.
         Readers are advised to review the philosophies underlying these methods discussed else-
         where [6.20]. In this book, the simplified method is used for determining wind pressure on
         building structures as needed.
           The walls for which the out-of-plane loads due to wind are to be determined are referred
         to as components and cladding in ASCE 7-05 Standard, which essentially are elements of
         the building envelope that do not qualify as parts of its MWFRS. For simplified method
         to be applicable to components and cladding of a building, it must meet the following
         criteria:

         1. The mean roof height h must not be greater than 60 ft (h ≤ 60 ft).
         2. The building is enclosed as defined in ASCE 7-05 Section 6.2 and conforms to wind-
           borne debris provisions of ASCE 7-05 Section 6.5.9.3.
         3. The building is a rectangular-shaped building as defined in ASCE 7-05 Section 6.2.
         4. The building does not have response characteristics making it subject to across-wind
           loading, vortex shedding, instability due to galloping or flutter, and does not have a site
           location for which channeling effects or buffeting in the wake of upwind obstructions
           warrant special consideration.
         5. The building has either flat roof, a gable roof with a slope equal to less than 45° with the
           horizontal, or a hip roof with a slope equal to or less than 27° with the horizontal.
           For components and cladding, the net wind pressure, p , to be applied to each building
                                                  net
         surface is given by Eq. (6.1):
                                   p  = lK Ip net30                   (6.1)
                                    net
                                          z t
         where   l =  adjustment factor for building height and exposure from  Table 6.1
                   (ASCE 7-05 Fig. 6-3)
               K  =  topographic factor as defined in ASCE 7-05 Section 6.5.7, evaluated at
                zt
                   mean roof height h
                 I = importance factor as defined in Table 6.2 (ASCE 7-05 Section 6.2)

              p net30  =  net design wind pressure for Exposure Category B, at h = 30 ft, and for
                   I = 1.0 from Table 6.2 (ASCE 7-05 Fig. 6-3)
           Values of l, I, and p net30  are given, respectively, in Tables 6.1 through 6.3. The topo-
         graphic factor, K , is given by Eq. (6.2):
                     zt
                                  K  = (1 + K K K ) 2                 (6.2)
                                   zt
                                          1
                                              3
                                            2
         where K , K , and K  are multipliers whose values are given in ASCE 7-05 Fig. 6-3, and
               1
                 2
                       3
         apply only when a hill or escarpment relative to upwind terrain is present. Where such a
         topographical characteristic is not present, the value of K  can be taken as 1.0, as assumed
                                                 zt
         for examples in this chapter.
   370   371   372   373   374   375   376   377   378   379   380