Page 385 - Design of Reinforced Masonry Structures
P. 385

6.36                       CHAPTER SIX

                                                  2
           Wall forces—Interior Zone 5 for effective area of 10 ft  (Table 6.3):
                               ⎧ ⎪  14 .6 lb/ft (inward pressure) ⎫ ⎪
                                        2
                         p    =  ⎨                     ⎬
                          net30  −      2
                               ⎩ ⎪  19 .5 lb/ft (outward pressure) ⎭ ⎪
                                            w
           Design wind pressure:
                               ⎧ ⎪ 115 146) = 168 lb/ft  2  (inward pressure)  ⎫ ⎪
                                          .
                                .
                                     .
                                   (
               w = p  = 1.15p net30  =  ⎨                         ⎬
                   net
                               ⎩ ⎪ 115(−119 5.) =− 22 4 lb/ft  2  (outward pressure )⎪
                                             .
                                                                  ⎭ ⎭
                                .
           b.  Calculate seismic load: Lateral seismic load on the wall would be calculated sepa-
             rately for the wall (w ) and for the parapet (w ).
                            u1
                                              u2
                                   w  = 0.4S IW p
                                          DS
                                    u1
           Determine short-period spectral acceleration parameter S :
                                                    DS
                                  S  = 150%g = 1.5g
                                   S
                                  S = 90%g = 0.90g
                                   1
                                     2
                                 S  =  / 3 S
                                  DS    MS
                                 S  = F S
                                      a S
                                  MS
           Site class is unknown; assume Site Class D.
           For Site Class D and S  ≥ 1.25g,
                           S
                               F  = 1.0 (ASCE 7-05 Table 11.4-1)
                                a
           Therefore,       S  = F S  = (1.0) (1.5g) = 1.5g
                                   a S
                              MS

                                         2
                                  2
                              S  =  / 3 S  =  / 3 (1.5g) = 1.0g
                                     MS
                               DS
           Determine 1-s period spectral acceleration parameter S :
                                                  D1
           For Site Class D and S  ≥ 0.25g,
                           1
                               F  = 1.5
                                v
           Therefore,       S  = F S  = (1.5) (0.9g) = 1.35g
                              M1   v 1
                                        2

                                  2
                              S  =  / 3 S  =  / 3 (1.35g) = 0.90g
                                     M1

                               D1
           For Occupancy Category III,
                                  I = 1.25 (Table 6.4)
           Determine the seismic design category: From ASCE 7-05 Table 11.6-1, for Occupancy
           Category III having S  ≥ 0.50g, SDC is D. From ASCE 7-05 Table 11.6-2, for Occupancy
                          DS
           Category III having S  ≥ 0.20g, SDC is D. Therefore, SDC for the building is D.
                          D1
                                       2
           The dead weight of the wall @ 84 lb/ft ,
                               W  = (84)(22.67) = 1904 lb
                                 p
              W  = 0.4S IW  = 0.4(1.25)(1904) = 952 lb (acting at the center of gravity)
                         p
               u1
                     DS