FUNDAMENTALS OF ELECTRIC SYSTEMS

                              FUNDAMENTALS OF ELECTRIC SYSTEMS            1.23

            Power in Three-Phase Systems
            The average power in a single-phase ac circuit is given by
                                       P   V I cos
                                       T    p p  p
            where   is the power factor angle. The total power delivered in a balanced three-phase cir-
                  p
            cuit is given by
                                     P   3 (V I cos   )
                                      T     p p   p
            The total power expressed in terms of line voltages and currents for a wye or delta con-
            nection is
                                     P    3  V I cos
                                      T      l l   p













































                   FIGURE 1.29 (a) Wye connection; (b) delta connection.