Page 73 - Electrical Equipment Handbook _ Troubleshooting and Maintenance
P. 73

TRANSFORMER COMPONENTS AND MAINTENANCE

            4.2                        CHAPTER FOUR

            ● Oil-immersed self-cooled (heat is removed by natural convection of the oil through radi-
              ators)
            ● Oil-immersed cooled by forced air (heat is removed by blowers blowing air on radiators)
            ● Oil-immersed cooled by water (the oil is cooled by an oil-water heat exchanger)
              The lowest rating of oil-type transformers is around 750 kVA. Since modern dry-type trans-
            formers are being manufactured up to a rating of 20 MVA, they are replacing oil-type
            transformers. The main reason is that oil-immersed transformers constitute a fire hazard, and
            they are very hard to maintain. Dry-type transformers are preferred in most industries.
              The rating of oil-immersed cooled-by-water transformers is normally higher than 100
            MVA. However, they could be used for transformers having a rating as low as 10 MVA if
            the transformer is feeding a rectifier. Harmonics (deformation in the sine wave of current
            and voltage) are normally generated in this application, causing significant heat generation,
            that necessitate cooling through a heat exchanger.
              Most failures in transformers are caused by erosion of the insulating materials. Analysis
            of a transformer’s oil can provide trends and early warning signs of premature failure.
            Figure 4.1 illustrates a basic electric power system from the utility to the consumer.


            MAIN COMPONENTS OF A POWER
            TRANSFORMER


            Figure 4.2 illustrates the outline drawing of a transformer. Figure 4.3 illustrates a cutaway
            view of an oil-filled transformer. The main components of the transformer are as follows:
             1. Concrete base. This is to provide support for the transformer. It must be leveled and
               fire-resistant.
             2. Core. It provides a route for the magnetic flux and supports the low-voltage and high-
               voltage windings.
             3. Low-voltage winding. It has fewer turns compared with the high-voltage windings. Its
               conductor has a large diameter because it carries more current.






















            FIGURE 4.1 Basic electric power system.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   68   69   70   71   72   73   74   75   76   77   78