Page 69 - Electrical Equipment Handbook _ Troubleshooting and Maintenance
P. 69

TRANSFORMERS

            3.26                      CHAPTER THREE

            magnetization current of the transformer. Figure 3.8a illustrates the magnetization curve of a
            transformer. When a voltage υ(t)   V sin 
t V is applied to the primary winding of the trans-
                                      M
            former, the flux will be


                                            V M
                                     (t)        cos 
t
                                            
N P
              A 5 percent increase in the applied voltage υ(t) will increase the flux in the core by 5
            percent. However, in the saturation region, a 5 percent increase in flux requires a much
            larger increase in the magnetization current than 5 percent (Fig. 3.23). Thus, at a specified
            voltage, this high magnetization current starts to damage the insulation. The rated voltage
            is determined by the maximum acceptable magnetization current.
              Since the flux is proportional to V/
, a transformer designed for 60-Hz operation can be
            operated on 50 Hz if the applied voltage is reduced by one-sixth. This is known as de-
            rating the transformer. Similarly, a transformer designed for 50-Hz operation can have 20
            percent higher voltage when operated at 60 Hz if its insulation system can withstand the
            higher voltage.








































            FIGURE 3.23 The effect of the peak flux in a transformer core upon the required magnetization current.



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   64   65   66   67   68   69   70   71   72   73   74