TRANSFORMERS

                                       TRANSFORMERS                       3.23

















                     FIGURE 3.19 A step-down connection.
            V . The current in this coil is called the series current I . The current and voltage on the
             SE                                     SE
            high-voltage side of the transformer are called I and V , respectively. The corresponding
                                              H     H
            parameters on the low-voltage side are called I and V , respectively. From Fig. 3.18b, the
                                              L    L
            voltages and currents in the coils are related by:
                                        V C

                                               N C
                                        V SE  N SE
                                       N I   N I
                                         C C  SE SE
            The voltages in the coils are given by
                                         V   V C
                                           L
                                       V   V   V
                                        H    C   SE
            The currents in the coils are given by
                                        I   I   I
                                        L   C   SE
                                          I   I
                                          H   SE
            The ratio of low and high voltage is given by


                                      V L
                                              N C

                                      V     N   N
                                       H     SE   C
            The ratio of low to high current is given by

                                           N SE   N C
                                      I L

                                      I H     N C
            THREE-PHASE TRANSFORMERS

            Most of the transformers used in power generation and distribution systems are three-phase.
            These transformers can be constructed from three single-phase transformers connected in a
            three-phase bank (Fig. 3.20). They can also be constructed by wrapping three sets of