Page 172 - Electrical Installation in Hazardous Area
P. 172

138  Electrical installations in hazardous areas

                     considered possible from the application of  Table 3.1 (if  it is decided that
                     it is acceptable in any given circumstance to have a building which is all
                     Zone 1).
                       If  it is not considered as acceptable for the entire building to be Zone 1,
                     then  each  primary  grade  source  of  release  must  have  local  ventilation
                     applied to remove the material released before it can access the generality
                     of  the building. In no circumstances is it considered possible to allow any
                     continuous grade source of  release to freely release into the building where
                     only general ventilation is present.
                       Having  determined  the  maximum  quantity  of  flammable  material
                     released into the building, it is then necessary to ensure that the amount
                      of  air supplied by the ventilation system is sufficient to ensure that, if  a
                     release occurs when the ventilation is on, the mixture of  air and flammable
                     material exhausted from the room is below the lower explosive limit and
                      it is wise to apply a safety factor here. Chapter 4 provides equations which
                     will allow this to be done. When the ventilation has been properly designed
                     it can be accepted that, provided that early repair of  the ventilation system
                     is executed so that it is not off  for a long time (say repair is to be completed
                     well within a shift), then a secondary grade release will not occur while
                     the ventilation is off  and there is little likelihood of  the building filling with
                     explosive atmosphere and then exhausting when the ventilation is switched
                     on, creating an explosive atmosphere outside the building. Unfortunately,
                     this does not hold for primary grade sources of  release and these must be
                     expected to release at times when the ventilation has failed but, as failure
                      of the ventilation is abnormal, such releases can be considered as secondary
                     grade  giving rise  to  Zone 2  within  the building  and  not  Zone 1.  There
                      remains, however, the problem that when the ventilation is repaired and
                      switched on, an explosive atmosphere will be exhausted from the building.
                     This, together with the fact that if input forced ventilation is used there will
                     be some leakage of  explosive atmosphere from within the building at all
                     openings, demands that any ventilation system used is extract ventilation
                     so that the pressure in the building will be very slightly lower than outside,
                      resulting in  release  of  explosive atmosphere to  the  outside  only  at  the
                     ventilation exhaust. Figs. 5.12 and 5.13 show how this situation exists in
                     practice.
                       Where only secondary grade sources of  release exist with general extract
                     ventilation,  the  inside  of  the  building  will  be  Zone 2  and  no  external
                     hazardous  area  will  exist.  Even  in  these  circumstances, however,  it  is
                     advisable to have an indirectly operated fan with the drive motor outside
                     the ducting and clear of  the ducting end, as if the ventilation fails for a long
                      time the fan will be necessary to remove a possible explosive atmosphere
                     from within the building. Although this is so unlikely as not to be within the
                      area classification considerations it is clearly not acceptable to use a source
                      of  ignition to try to clear an explosive atmosphere, however unlikely that
                     atmosphere may be.
                       Where primary grade sources of  release exist without local ventilation,
                     as described earlier, the inside of  the building will be Zone 1 and a Zone 2
   167   168   169   170   171   172   173   174   175   176   177