Page 173 - Electrical Installation in Hazardous Area
P. 173

Area classification in areas which are not freely ventilated  139

                                              /--                     Extract
                                                                      aidlow
                                                                      Ihlnt.3  3)
                                      Buildina  bE(



                                                           Crack
                                                           +--  (Note



                           (Note
                                                          Air inlet __.
                                                                (Note I)
                               Door
                                                        Ground
                  Fig. 5.12  Secondary  grade  source  of  release  with  forced  ventilation.  Notes: (1)
                          Extract ventilation ensures that airflow at all apertures will be into building.
                          (2) Extract airflow sufficient to dilute maximum secondary grade source of
                          release to required fraction of  LEL


                                                           Extract
                                                            air   +





                                                                       (Note 2)





                                                                         Air inlet
                                                                    -(Note   1)






                                                                         Air inlet
                                                                    -(Note   1)
                                     Ground
                          a = Table  3.2 but 0.5 m minimum
                  Fig. 5.13  Primary  grade  source  of  release  with  extract  ventilation.  Notes: (1)
                          Ventilation  ensures  airflow  is  into  the  building  in  normal  operation
                          restricting  Zone 1  to  inside  building.  (2) In  abnormal  circumstances
                          explosive atmosphere may leak from extract vent  in addition to building
                          openings