Page 244 - Electrical Safety of Low Voltage Systems
P. 244

Testing the Electrical Safety    227







































                                  FIGURE 14.5 Fall of potential method to determine the earth resistance.


                                  current electrode Z must be away from X by a distance d large enough
                                  so that they are independent of each other, and the total earth poten-
                                  tial curve will be characterized by a flat region. Based on what was
                                  studied in Chap. 4, if the earth electrode under test is a rod, the inde-
                                  pendency will be guaranteed if d is at least five times the rod’s length.
                                  If the electrode being examined has a more complex structure (e.g., an
                                  earthing grid), the minimum distance to be considered is five times its
                                  maximum diagonal, or five times the diameter of a circle of equivalent
                                  area.
                                     The potential probe Y must be driven in a point at zero potential
                                  (flat portion of the earth potential distribution in Fig. 14.5), that is,
                                  outside of both the influence areas of X and Z. Erroneous values for
                                  R G will be obtained if Y is placed too close to X, or too far from X.
                                     For example, let us consider Fig. 14.6 where Y is too close to X.
                                  The potential difference measured by the tester is lower than V T , thus
                                  the instrument will return an incorrect lower value for R G .IfYand X
                                  coincided, the tester would measure zero.
   239   240   241   242   243   244   245   246   247   248   249