Page 247 - Electrical Safety of Low Voltage Systems
P. 247

230    Chapter Fourteen


                                  is effective in preventing parts of fault currents from flowing through
                                  ground, thereby lowering touch and step voltages at the user’s
                                  premises. During the measurement, this connection must be removed
                                  at both ends, so that the entire test current will return to the source
                                  through the earth, allowing the proper determination of the unknown
                                  ground grid resistance.


                             14.5 Earth Resistance Measurement in TT Systems
                                  As discussed in Chap. 6, the fault-loop in TT systems includes both
                                  the ground resistance R G of the consumer’s electrode and the utility’s
                                  electrode earth resistance R N , which are independent of each other
                                  (Fig. 6.1). In the assumption that R G 	 R N , which holds true especially
                                  in urban areas, a simplified method to measure the earth resistance of
                                  the user’s electrode may be adopted.
                                     With the aforementioned method, which does not require any aux-
                                  iliary electrode, the total fault-loop resistance is measured, and the
                                  result will basically coincide with R G (Fig. 14.9).
                                     The voltmeter V in Fig. 14.9 measures the phase voltage V ph
                                  (switch in open position) and then after closing the switch the fall
                                  of potential V R across the resistance of the potentiometer R, of known
                                  value, caused by the test current I G . I G must not exceed the operating
                                  threshold of the RCD in order to prevent this protective device from
                                  tripping during the test.
                                     Thus, by applying Ohm’s law, we obtain


                                                              V ph
                                                     V R =           × R               (14.4)
                                                          R N + R G + R
























                                  FIGURE 14.9 Fault-loop resistance test in TT systems.
   242   243   244   245   246   247   248   249   250   251   252