Page 252 - Electrical Safety of Low Voltage Systems
P. 252

Testing the Electrical Safety    235
























                                  FIGURE 14.13 Test circuit to measure touch voltages in TN systems.


                                  the same way as discussed in Sec. 14.6. At the same time, the voltage
                                  between the ECP and the EXCP is measured by the voltmeter V 1 .As
                                  already explained in Chap. 4, the voltmeter V 1 has a 1-k  resistance
                                  connected in parallel to its leads to simulate the conventional body
                                  resistance of a standard person.
                                     By knowing |Z Loop |, the actual fault current |I G |, which is greater
                                  than |I|, can be so determined:


                                                                |V |
                                                                  ph
                                                         |I |=                        (14.14)
                                                          G
                                                               |Z   |
                                                                 Loop
                                     Assuming a linear relationship between currents and voltages, the
                                  magnitude of the touch voltage V T at the measurement point can be
                                  calculated as:

                                                                |I |
                                                                  G
                                                          V T = V 1                   (14.15)
                                                                 |I|
                             14.8 Step and Touch Voltage Measurements
                                   in TN Systems
                                  As already substantiated in Chap. 7, ground faults that occur on the
                                  primary side of substations may cause circulation of high currents in
                                  their earthing systems, thereby causing touch and step voltages. The
                                  magnitude of such quantities must be ascertained via field tests and
                                  compared against values considered safe by applicable standards.
   247   248   249   250   251   252   253   254   255   256   257