Page 255 - Electrical Safety of Low Voltage Systems
P. 255

238    Chapter Fourteen








                                                                               β



                                  FIGURE 14.17 Triangle obtained by composing together the phasor diagrams
                                  of Figs. 14.16 and 14.17.

                                     By composing together the two previous phasor diagrams, which
                                  have in common the magnitudes of V d and V, we obtain the following
                                  triangle, whose base equals 2|V d |.
                                     |V| will coincide with the triangle’s median, whose length is given
                                  by


                                                            V 1 2  V 2 2
                                                      V =      +    − V d 2           (14.18)
                                                            2    2
                                  Equation (14.18) provides the correct value that should be used in
                                  Eq. (14.16).


                             14.9 Fundamental Measurements in IT Systems
                                  As examined in Chap. 9, under first-fault conditions, safety against
                                  indirect contact in IT systems is assured if

                                                                50
                                                           R G ≤                      (14.19)
                                                                I G
                                  where R G is the earth resistance of the grounding system and I G is the
                                  first-fault current to ground.
                                     To guarantee the fulfillment of Eq. (14.18), I G must be measured.
                                  A typical testing circuit using a clamp-on current meter is shown in
                                  Fig. 14.18.
                                     During this measurement, a line conductor is gradually connected
                                                    3
                                  to earth via a rheostat R. When the rheostat is fully disengaged (i.e.,
                                  zero resistance), the clamp-on current meter reads the first-fault cur-
                                  rent. The presence of the rheostat is advisable in order to prevent the
                                  inception of a short circuit, in the eventuality that a nonresolved first
                                  fault involving another phase conductor should still exist in the sys-
                                  tem at the time of the test.
                                     As previously explained in Chap. 9, under first-fault conditions,
                                  the IT system “evolves” into a TT (ECPs earthed individually, or in
   250   251   252   253   254   255   256   257   258   259   260