Page 251 - Electrical Safety of Low Voltage Systems
P. 251

234   Chapter Fourteen






















                                  FIGURE 14.12 Test circuit to measure the fault-loop impedance in
                                  de-energized TN systems.

                                  The numerator represents the much simpler algebraic difference be-
                                  tween the magnitudes of the two voltages.
                                     In the case of a prevalently resistive fault-loop, ohmmeters, per-
                                  forming the measurement as per Eq. (14.13), may be used for the test.
                                  If the loop is also reactive, for instance near large transformers (i.e.,
                                  >100 kVA), loop-testers performing the test as per Eq. (14.12) should
                                  be employed in order to prevent errors in the measurement.
                                     A more rigorous method of measurement of the fault-loop
                                  impedance employs loop-testers with a built-in independent genera-
                                  tor G at the power system frequency. In this case, one must disconnect
                                  the supply to the primary side of the transformer and short circuit its
                                  windings (Fig. 14.12).
                                     The fault-loop impedance is directly given by the ratio of the read-
                                  ings of voltage and current. A major drawback of this method is the
                                  necessity to put the substation out of service.


                             14.7 Touch Voltage Measurement in TN Systems
                                   (Low-Voltage Earth Faults)
                                  The measurement of the actual touch voltage for the worst-case sce-
                                  nario of hand-to-hand contacts occurring between ECPs (e.g., low-
                                  voltage panels) and EXCPs (e.g., cold water pipes) can be carried out
                                  with the method of the fall of potential (Fig. 14.13). If the measure-
                                  ment’s result does not exceed 50 V, the installation can still be consid-
                                  ered safe against indirect contact, even if |Z Loop | is not in compliance
                                  with Eq. (7.5).
                                     With this arrangement, the test current I will circulate through
                                  the protective conductor and the loop impedance will be measured in
   246   247   248   249   250   251   252   253   254   255   256