Page 256 - Electrical Safety of Low Voltage Systems
P. 256

Testing the Electrical Safety    239




























                                  FIGURE 14.18 Test circuit to measure the first-fault current with clamp-on
                                  current probe in IT systems.


                                  groups) or into a TN (ECPs collectively earthed). In the first case,
                                  the fulfillment of Eq. (9.22) must be verified by measuring the earth
                                  resistance of the local grounding system, as explained in Sec. 14.5.
                                     In the most common case of ECPs collectively earthed, the fulfill-
                                  ment of Eq. (9.24) (i.e., neutral wire not shipped to loads) or Eq. (9.26)
                                  (i.e., neutral wire shipped to loads) must be verified. In either case,

                                  the fault-loop impedances Z S and Z must be measured.
                                                                S
                                     A typical testing arrangement for IT systems with no neutral con-
                                  ductor is shown in Fig. 14.19.
                                     For the duration of the test, a temporary connection between the
                                  neutral point and the earth must be carefully realized in order to close
                                  the fault-loop otherwise open by definition.




                             14.10 Protective Conductor Continuity Test
                                  As already substantiated in previous chapters, protection against in-
                                  direct contact for Class I equipment requires both the basic insulation
                                  of live parts and an effective link to the means of earthing, via the
                                  protective conductor (PE) in the connecting cable and plug, as well
                                  as in the socket outlet. In addition, main (MEB) and supplementary
                                  (SB) bonding conductors must be present to ensure equipotentiality
                                  between ECPs and EXCPs in fault conditions.
   251   252   253   254   255   256   257   258   259   260   261