Page 245 - Electrical Safety of Low Voltage Systems
P. 245

228    Chapter Fourteen






















                                  FIGURE 14.6 The potential probe Y is placed too close to X.


                                     On the other hand, if Y and Z coincided, the tester would provide
                                  the summation of the earth resistances of both the electrode under
                                  test and the auxiliary electrode, hence presenting an incorrect higher
                                  value for R G .
                                     To locate the point at zero potential, the operator must take suc-
                                  cessive readings after moving the potential probe Y toward Z. The flat
                                  region of the earth potential is found when subsequent readings of R G
                                  do not appreciably change.



                             14.4 Earth Resistance Measurements
                                   in Industrial Facilities
                                  In industrial facilities generally characterized by grounding grids, the
                                  earth resistance measurement can be facilitated in the presence of
                                  metal bodies embedded in the earth (e.g., EXCPs such as underground
                                  cold water pipes). If such metalwork extends well beyond the facil-
                                  ity’s area and has an estimated negligible resistance-to-ground (i.e.,
                                  R EXCP 
 R G ), it can be used at the same time both as a current and as
                                  a potential electrode (Fig. 14.7).
                                     The tester will measure the sum of the earth resistances of both
                                  the electrode under test and the EXCP, which, in the above assump-
                                  tions, will practically coincide with the resistance-to-ground of the
                                  electrode under test. Alternatively, the low-voltage neutral of a neigh-
                                  boring utility substation, or even of a dwelling unit, can be used as a
                                  simultaneous current and potential electrode. In this case, the neutral
                                  must be checked to assure its de-energization.
                                     Grounding grids in industrial facilities may have a very large ex-
                                  tension (e.g., perimeters of several hundreds of meters). Therefore,
   240   241   242   243   244   245   246   247   248   249   250