Page 125 - Estimators Piping Man Hour Manual
P. 125

IOS   Section Two-FIELD FABRICATION

                              'OLET TYPE     WELDS


                                 Labor Cutting And Welding
                                   Carbon Steel Material

                                 NET MAN HOURS EACH
                Nominal Pipe Size         Standard    Extra  Strong  Greater Than
                                           Weight        and       Extra Strong
           Outlet         Header         And 2000 #     3000 #      and 6000 #
           1/2     All Sizes                 1.5          2.0          2.5
           3/4     All Sizes                 1.8          2.2          3.0
           1       All Sizes                2.1           2.5          3.3
           1-1/4   All Sizes                2.3           2.9          3.8
           1-1/2   All Sizes                2.9           3.7          4.9
           2       All Sizes                3.9           4.8          6.4
           2-1/2   All Sizes                4.6           5.9          7.7
           3       All Sizes                5.3           6.8          10.6
           4       All Sizes                 7.0          8.5          11.3
           5       All  Sizes               7.9           9.3          13.7
           6       All Sizes                8.7           9.9          16.0
           8       All Sizes                9.7          10.6          18.9
           10      All Sizes                13.6         19.4          30.2
           12      All Sizes                19.0         22.5          44.7
           14      14' And 16"              23.8         26.5          53.9
           14      18" And Larger           21.2         23.8          58,7
           16      16" And  18"             28.4         30.4          70.4
           16      20" And Larger           25.1         27.4          76.2
           18      18" And 20"              33.7         36.9          91.0
           18      24 "And Larger           29.7         32.7          98.0
           20      20 "And 24"              40.9         44.9         100.9
           20      26" And Larger           35.7         39.9         108.8
           24      24 "And 26"              62.7         73.3         121.1
           24      28 "And Larger           52.8         63.4         130.5
      Man  hours are based on the outlet size and schedule except when the  run  schedule is greater than the outlet
      schedule, in which case the man hours are based on the outlet size and run schedule.
      For elbolet or latrolet  welds and weldolets, thredolets, etc., that are attached to fittings or welded at any angle
      other than 90°, add 50% to the above man hours.
      For sweepolet attachment welds, add 150% to the above man hours.
   120   121   122   123   124   125   126   127   128   129   130