Page 467 - Subyek Teknik Mesin - Forsthoffers Best Practice Handbook for Rotating Machinery by William E Forsthoffer
P. 467

Be st Practice 7 .32          Lube, Seal and Control Oil System Best Practices


         Best Practice 7.32Practice 7.32Practice 7.32
         Best
         Best
         Use multiple solenoid control oil dump valves in parallel  Lessons Learned
         and in series, with on-line solenoid test facilities for each  Malfunctioning solenoid valve trip control systems have
         valve, to ensure optimum reliability of the trip system.  been responsible for catastrophic turbine failures and
           One solenoid valve installed in the control oil system exposes the  spurious trips on low control oil pressure due to solenoid
         turbine to a spurious trip if the solenoid should open, and to cata-  valve failures.
         strophic damage if the valve fails to open on command.
                                                              The majority of older control oil trip systems used neither parallel
           Installing two solenoid valves in parallel significantly increases the
                                                            trip valves nor on-line test facilities.
         reliability of the system since only one valve has to open to trip the
         turbine on command. However if one valve opens when not required,  Benchmarks
         a trip can occur.
                                                            This best practice has been used since 1997, when research into the
           Installing two solenoid valves in parallel with another valve in series
                                                            causes of turbine trips showed that the highest cause of turbine trips
         in each loop (total four (4) solenoid valves) will result in the highest trip  were improper functioning of the solenoid trip valves in single and
         system reliability, since this will provide optimum assurance that one  parallel trip systems.
         valve will open on command in addition to preventing an incidental
         solenoid valve opening.
           In addition, having an on-line solenoid test for each valve every
         three months will provide optimum assurance that the solenoid trip
         system will function as necessary.







       B.P. 7.32. Supporting Material

                                                              This system incorporates a mechanical overspeed device
       Protection                                           (trip pin) to shut down the turbine on overspeed (10% above
                                                            maximum continuous speed). Centrifugal force resulting from
       The function of the steam turbine protection system is often  high shaft speed will force the trip lever which will allow the
       confused with the control system, but the two systems are  spring loaded handle to move inward. When this occurs, the
       entirely separate. The protection system only operates
                                                            port in the handle stem will allow the control oil pressure to
       when any of the control system set point parameters  drain and drop to zero. The high energy spring in the trip and
       are exceeded and the steam turbine will be damaged if it  throttle valve, normally opposed by the control oil pressure will
       continues to operate. Figure 7.32.1 defines the typical pro-  close suddenly (less than 1 second). In this system there are
       tection methods.                                     two other means of tripping the turbine (reducing control oil
                                                            pressure to 0 PSI):
                                                            - Manually pushing spring loaded handle
        The protection system monitors steam turbine total train  - Solenoid valve opening
        parameters and ensures safety and reliability by the following
        action:                                               The solenoid valve will open on command when any trip
           Start-up (optional) provides a safe, reliable fully automatic start-  parameter set point is exceeded. Solenoid valves are designed to
           up and will shut down the turbine on any abnormality  be normally energized to close.
           Manual shutdown                                    In recent years the industry has required a parallel and series
           Trip valve exerciser allows trip valve stem movement to be  arrangements of solenoid valves to ensure increased steam tur-
           confirmed during operation without shutdown       bine train reliability. Figure 7.32.3 shows two popular methods
           Rotor overspeed monitors turbine rotor speed and will shut
           down turbine when maximum allowable speed (trip speed) is  of overspeed protection used in the past.
           attained                                           Most speed trip systems now incorporate magnetic speed
           Excessive process variable signal monitors all train process  input signals and two-out-of-three voting for increased re-
           variables and will shut down turbine when maximum value is  liability. Figure 7.32.4 presents the devices that trip the turbine
           exceeded                                         internally. That is, they directly reduce the control oil pressure
                                                            causing a trip valve closure without the need of a solenoid valve
                                                            (external trip method).
       Fig 7.32.1   Protection
                                                              Two popular types of steam turbine shutoff valves are shown
                                                            in Figure 7.32.5. Both types use a high spring force, opposed by
          A schematic of a multi-valve, multi-stage turbine protection  control oil pressure during normal operation, to close the valve
       system is shown in Figure 7.32.2.                    rapidly on loss of control oil pressure.


           438
   462   463   464   465   466   467   468   469   470   471   472