Page 22 - Handbook of Electrical Engineering
P. 22

1




           Estimation of Plant Electrical Load









           One of the earliest tasks for the engineer who is designing a power system is to estimate the normal
           operating plant load. He is also interested in knowing how much additional margin he should include
           in the final design. There are no ‘hard and fast’ rules for estimating loads, and various basic questions
           need to be answered at the beginning of a project, for example,

           • Is the plant a new, ‘green field’ plant?
           • How long will the plant exist e.g. 10, 20, 30 years?
           • Is the plant old and being extended?
           • Is the power to be generated on site, or drawn from an external utility, or a combination of both?
           • Does the owner have a particular philosophy regarding the ‘sparing’ of equipment?
           • Are there any operational or maintenance difficulties to be considered?
           • Is the power factor important with regard to importing power from an external source?
           • If a generator suddenly shuts down, will this cause a major interruption to the plant production?
           • Are there any problems with high fault levels?


           1.1 PRELIMINARY SINGLE-LINE DIAGRAMS

           In the first few weeks of a new project the engineer will need to roughly draft a key single-line
           diagram and a set of subsidiary single-line diagrams. The key single-line diagram should show the
           sources of power e.g. generators, utility intakes, the main switchboard and the interconnections to
           the subsidiary or secondary switchboards. It should also show important equipment such as power
           transformers, busbars, busbar section circuit breakers, incoming and interconnecting circuit breakers,
           large items of equipment such as high voltage induction motors, series reactors for fault current
           limitation, and connections to old or existing equipment if these are relevant and the main earthing
           arrangements. The key single-line diagram should show at least, the various voltage levels, system
           frequency, power or volt-ampere capacity of main items such as generators, motors and transformers,
           switchboard fault current levels, the vector group for each power transformer and the identification
           names and unique ‘tag’ numbers of the main equipment.
                 The set of single-line diagrams forms the basis of all the electrical work carried out in a
           particular project. They should be regularly reviewed and updated throughout the project and issued

           Handbook of Electrical Engineering: For Practitioners in the Oil, Gas and Petrochemical Industry.  Alan L. Sheldrake
            2003 John Wiley & Sons, Ltd ISBN: 0-471-49631-6