Page 23 - Handbook of Electrical Engineering
P. 23

2    HANDBOOK OF ELECTRICAL ENGINEERING

                                 Table 1.1.  Voltages used in different countries for generation,
                                 distribution and transmission
                                 Low voltage        High voltage     High voltage
                                 generation and    generation and    transmission
                                 three-phase        distribution    less than 75 kV
                                 consumers (volts)   (kilovolts)      (kilovolts)
                                 910               18       7.2 ∗   70      24.5
                                660                16       6.9     69 ∗    24
                                600 ∗              14.4     6.6 ∗   66 ∗    23
                                525                13.8 ∗   6.5     65      22
                                500                13.2 ∗   6.3     60      20
                                480                12.6     6.24    50      19
                                460                12.5     6 ∗     46      15
                                440 ∗              12.47    5.5     45
                                420                12.4     5       44
                                415 ∗              12       4.8     38
                                400 ∗              11.5     4.16 ∗  36
                                380 ∗              11.4     4       35
                                346                11 ∗     3.3 ∗   34.5 ∗
                                 277               10.4     3 ∗     33 ∗
                                 260               10       2.4     31.5
                                 254 ∗∗             9       2.3     30
                                240 ∗∗              8.9             27.6
                                230 ∗∗              8.4             27.5
                                220 ∗∗              8.3             27
                                208                 8               25
                                200                 7.3             24.9
                                190
                                 Notes ∗  Commonly used voltages in the oil industry.
                                Notes ∗∗  Commonly used as single-phase voltages.


              in their final form at the completion of the project. They act as a diary and record the development
              of the work. Single-line diagrams are also called ‘one-line diagrams’.
                    At this stage the engineer can begin to prepare a load schedule for each subsidiary switchboard
              and motor control centre, and a master schedule for the main switchboard. The development of the
              single-line diagrams during the project is discussed in sub-section 1.7.

                    The master load schedule will give an early estimate of the total power consumption. From
              this can be decided the number of generators and utility intakes to install. The kW and kVA ratings
              of each generator or intake will be used to determine the highest voltage to use in the power
              system. Table 1.1 shows typical voltages used throughout the world for generation, distribution and
              transmission of power at oil industry plants, see also sub-section 3.7.


              1.2 LOAD SCHEDULES

              Each switchboard will supply power to each load connected to it and in many cases it will also supply
              power to switchboards or distribution boards immediately downstream. Hence the input power to a