Page 24 - Handbook of Electrical Engineering
P. 24

ESTIMATION OF PLANT ELECTRICAL LOAD     3

           switchboard will have the possibility of two components, one local and one downstream. Hereinafter
           the term switchboard will also include the term motor control centre, see sub-section 7.1.
                 Each local load may be classified into several different categories for example, vital, essential
           and non-essential. Individual oil companies often use their own terminology and terms such as
           ‘emergency’ and ‘normal’ are frequently encountered. Some processes in an oil installation may
           handle fluids that are critical to the loss of power e.g. fluids that rapidly solidify and therefore must
           be kept hot. Other processes such as general cooling water services, air conditioning, sewage pumping
           may be able to tolerate a loss of supply for several hours without any long-term serious effects.

                 In general terms there are three ways of considering a load or group of loads and these may
           be cast in the form of questions. Firstly will the loss of power jeopardise safety of personnel or
           cause serious damage within the plant? These loads can be called ‘vital’ loads. Secondly will the loss
           of power cause a degradation or loss of the manufactured product? These loads can be called the
           ‘essential’ loads. Thirdly does the loss have no effect on safety or production? These can be called
           the ‘non-essential’ loads.
                 Vital loads are normally fed from a switchboard that has one or more dedicated generators
           and one or more incoming feeders from an upstream switchboard. The generators provide power
           during the emergency when the main source of power fails. Hence these generators are usually
           called ‘emergency’ generators and are driven by diesel engines. They are designed to automatically
           start, run-up and be closed onto the switchboard whenever a loss of voltage at the busbars of the
           switchboard is detected. An undervoltage relay is often used for this purpose. Testing facilities are
           usually provided so that the generator can be started and run-up to demonstrate that it is ready to
           respond when required. Automatic and manual synchronising facilities can also be provided so that
           the generator can be loaded during the tests.

                 Low voltage diesel generators are typically rated between 100 and 500 kW, and occasionally
           as large as 1000 kW. High voltage emergency generator ratings are typically between 1000 and
           2500 kW. The total amount of vital load is relatively small compared with the normal load and, in
           many situations, the essential load. Consequently the vital load is fed from uninterruptible power
           supplies (UPS), as AC or DC depending upon the functions needed. The vital loads are usually fed
           from a dedicated part of the emergency switchboard. The UPS units themselves are usually provided
           with dual incoming feeders, as shown in Figure 17.3.
                 Some of the vital and essential loads are required when the plant is to be started up, and there
           is no ‘normal’ power available. In this situation the starting up of the plant is called ‘black starting’.
           The emergency generator must be started from a source of power, which is usually a high capacity
           storage battery and a DC starter motor, or a fully charged air receiver and a pneumatic starter motor.
                 In many plants, especially offshore platforms, the vital and essential loads operate at low
           voltage e.g. 380, 400, 415 volts. Large plants such as LNG refrigeration and storage facilities require
           substantial amounts of essential power during their start-up and shut-down sequences and so high
           voltage e.g. 4160, 6600 volts is used. The vital loads would still operate at low voltage. Tables 1.2
           and 1.3 shows typical types of loads that can be divided into vital and essential loads.

           All of the vital, essential and non-essential loads can be divided into typically three duty categories:
           • Continuous duty.
           • Intermittent duty.
           • Standby duty (those that are not out of service).
   19   20   21   22   23   24   25   26   27   28   29