6    HANDBOOK OF ELECTRICAL ENGINEERING

                           Table 1.5.  Subsidiary load schedule for the low voltage process switchboard

              Description of load            No. of   Nameplate   Continuous  Intermittent  Standby
                                              units   ratings of    power       power       power
                                                      each unit   consumed     consumed    consumed
                                                        (kW)        (kW)         (kW)        (kW)
              Production area lighting         2         75          150           0           0
              Glycol pumps                     4          2           4            0           4
              Glycol reboilers                 2         75          75            0          75
              Glycol transfer pump             1         15          15            0           0
              Refrigeration compressor         3        160          320           0         160
              Deareator vacuum pumps           2         30          30            0          30
              Water injection booster pumps    4         90          270           0          90
              Deareator chem. injection pumps  4          2           4            0           4
              Sea drain sump pumps             1         10          10            0           0
              Water inj. chem. injection pumps  6         2           8            0           4
              Reclaim oil pumps                2         37          37           37           0
              Treated water pumps              2        132          132         132           0
              Oil transfer pumps               4         10          30           10           0
              Electric gas heating             2        300          300           0         300
              HP gas comp. pre-lube pumps      2          5           5            0           5
              2 × HP gas comp. auxiliaries     2         —           35           35         100
              LP gas comp. pre-lube pumps      2          5           5            0           5
              2 × LP gas comp. auxiliaries     2         —           35           35         100
              4 × water inj. pump auxiliaries  4         —           70           70         200
              Corrosion inhibitor pumps        1         37          37            0           0
              Trace heating                    2         40          80            0           0

              Sub-totals for the switchboard                        1652         319        1077
              Normal running load for the switchboard = (1.0 × 1652) + (0.5 × 319) + (0.1 × 1077) = 1920 kW

                           Table 1.6.  Subsidiary load schedule for the low voltage utilities switchboard
              Description of load            No. of   Nameplate   Continuous  Intermittent  Standby
                                              units   ratings of    power       power       power
                                                      each unit   consumed     consumed    consumed
                                                        (kW)        (kW)         (kW)        (kW)
              Utilities area lighting          2         75          150           0           0
              Potable water pumps              2          5           5            5           0
              Living quarters feeder-A(on)     1        500          300         200           0
              Living quarters hot water pumps  2         15          15           15           0
              Control room supplies            1         15          15            0           0
              Computer supplies                2         15          15            0          15
              Radio supplies                   2         30          30            0          30
              Instrument air compressor        2         90          90            0          90
              Instrument air driers            2         10          10            0          10
              Plant air compressors            2         90          90            0          90
              HVAC fans                       16         11          88            0          88
              HVAC main air handling unit      1         30          30            0           0
              HVAC standby air handling unit   1         10           0            0          10
              HVAC refrigeration unit          1         15          15            0           0
              Gas turbo-generator auxiliaries  4         —           100         100         300
              Trace heating                    2         30          60            0           0
              Sub-totals for the switchboard                        1013         320         600
              Normal running load for the switchboard = (1.0 × 1013) + (0.5 × 320) + (0.1 × 633) = 1236 kW