Page 62 - Handbook of Electrical Engineering
P. 62

GAS TURBINE DRIVEN GENERATORS      41

                                  Table 2.5.  Open-loop steady state speed-power
                                  characteristic of a gas turbine (k = 0.1)
                                  Shaft power      Shaft speed ω (per unit)
                                  P (per unit)
                                                Positive root  Negative root

                                    0.0           1.10           0.0
                                    0.5           1.0525         0.0475
                                    0.75          1.027          0.073
                                    1.00          1.000          0.100
                                    1.04          0.9955         0.1045
                                    1.50          0.9405         0.1550
                                    2.00          0.8700         0.2300
                                    3.00          0.6000         0.5000
                                    3.025         0.5500         0.0



                 At P = 1.0 the torque corresponding to the positive root is T = 0.667 pu, whilst that for the
           negative root is T = 1.00 pu. Hence the torque at full-load power is less than unity (due to the
           speed being higher than unity). The above example illustrates the impractical nature of the open-loop
           speed-torque and speed-power characteristics.
                 Suppose the design of the engine could be substantially improved such that k could be reduced
           to say 0.1 (approaching a value for a typical closed-loop feedback controlled system). Table 2.5 shows
           comparable results to those given in Table 2.4.
                 It can be seen that unit power is obtained at unit speed in the stable region, and that the stalling
           point is at a power much greater than unity. The above illustrates more desirable open-loop speed-
           torque and speed-power characteristics. Unfortunately reducing k to values between say 0.01 and
           0.1 by thermodynamic design is not practical. Consequently a closed-loop feedback control system
           is necessary. Figure 2.12 shows the open-loop speed-power responses for different values of k.The
           transient response of the gas turbine just after a disturbance in the shaft power is of interest when
           underfrequency protective relays are to be used to protect the power system from overloading, see
           sub-section 12.2.10.



           2.5.2 Closed-loop Speed-power Characteristic

           All prime-moves used for driving electrical generators are equipped with closed-loop speed governors.
           Their main purpose is to reduce the variation in shaft speed to a small amount over the full range of
           shaft power. Deviations in speed are measured and amplified. The amplified signal is used to operate
           the fuel value in such a manner as to reduce the deviation in speed. It may be assumed that a linear
           relationship exists between the amplified signal received at the value and the shaft power created by
           the fuel passed through the valve orifice. The fuel valve may be regarded as a regulating device for
           power available at the shaft. It may therefore be assumed that the output of the valve is the shaft
           power P , whilst its inputs are a reference power P ref and the amplified speed error P e .
                 Therefore,
                                               P = P ref − P e                            (2.53)
   57   58   59   60   61   62   63   64   65   66   67