Page 148 - Handbook of Structural Steel Connection Design and Details
P. 148

Design of Connections for Axial, Moment, and Shear Forces

                           Design of Connections for Axial, Moment, and Shear Forces  133

                                             5
                      Beam web. To support a  / fillet weld on both sides of a plate, AISC
                                              16
                    LRFD Manual Table 10.2 shows that a 0.476-in web is required. For a
                    5 / fillet on one side, a 0.238-in web is required. Since the W21   62 web
                     16
                    is 0.400 in thick, it is ok.
                      Beam nos. 3 and 4 W21   44 (G50) composite. The flange connection is a full
                    penetration weld, so again, no design is required. Section A-A of Fig.
                    2.33a shows the arrangement in plan. See Fig. 2.33c. The connection
                                      1
                    plates A are made  / in thicker than the W21   44 beam flange to
                                        4
                    accommodate under and over rolling and other minor misfits. Also, the
                                                                             3
                    plates are extended beyond the toes of the column flanges by  / to 1 in
                                                                              4
                    to improve ductility. The plates A should also be welded to the column
                    web, even if not required to carry load, to provide improved ductility. A
                    good discussion of this is contained in the AISC 13th Edition Manual of
                    Steel Construction, pp. 12-14 through 12-19.
                      The flange force for the W21   44 is based on the full moment capac-
                    ity as required in this example, so  M   358 kips-ft. For gravity
                                                          p
                    moments, the beam moments counteract each other, and the column
                    bending strength is not an issue. For lateral moments, however, the
                    beam moments add, and the column strength may limit the beam
                    moments. The weak-axis column design strength is
                                                50
                                    M 5 0.9 3      3 83.6 5 314 kips-ft
                                      p
                                                12
                      Therefore, for lateral loads, the beam plastic moment cannot be
                    achieved because 2   358 > 2   314.
                      For lateral loads, the maximum beam moment is  M   314 kips-ft.
                                                                       b
                      In summary, for gravity loads,  M   M   358 kips-ft and the flange
                                                    b      p
                    force is
                                             358 3 12
                                       F 5               5 212 kips
                                        f
                                            s20.7 2 0.45d
                    and for lateral loads,  M   314 kips-ft and the flange force is
                                           b
                                             314 3 12
                                      F 5                5 186 kips
                                       f
                                           s20.7 2 0.450d
                      Figure 2.36 shows the distribution of forces on the plates A, including the
                    forces from the strong axis connection. The weak axis gravity force of 212
                    kips is distributed one-fourth to each flange and one-half to the web. This
                    is done to cover the case when full gravity loads are not present on each
                    side. In this case, all of the 212 kips must be passed to the flanges. To see
                    this, imagine that beam 4 is removed and the plate A for beam 4 remains
                    as a back-up stiffener. One half of the 212 kips from beam 3 passes into the
                    beam 3 near side column flanges, while the other half is passed through



                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.accessengineeringlibrary.com)
                             Copyright © 2009 The McGraw-Hill Companies. All rights reserved.
                              Any use is subject to the Terms of Use as given at the website.
   143   144   145   146   147   148   149   150   151   152   153