Design of Connections for Axial, Moment, and Shear Forces

                           Design of Connections for Axial, Moment, and Shear Forces  129

                      Web yielding:  P    P    t P   167   0.615   24.3   182 kips
                                     wy    wo   b  wi
                    229 kips, thus stiffeners are required at both flanges.
                      Web buckling:  P    260 kips > 229 kips   no stiffener required at
                                      wb
                    compression flange.
                      Flange bending: P   171 kips   229 kips   stiffener required at ten-
                                       fb
                    sion flange.
                      From the preceding three checks (limit states), a stiffener is required
                    at both flanges. For the tension flange, the total stiffener force is 229
                    171   58 kips and for the compression flange, the stiffener force is 229
                    189   40 kips. But the loads may reverse, so use the larger of 58 and
                    40 as the stiffener force for both flanges. Then, the force in each stiff-
                           58
                    ener is  /   29 kips, both top and bottom.
                             2
                      Determination of stiffener size. The minimum stiffener width w is
                                                                             s
                                          t     8.24   0.485
                                     b fb  wc
                                        2     5      2       5 2.5 in
                                      3    2     3       2
                                   1
                    Use a stiffener 6 / 2 in wide to match column.
                      The minimum stiffener thickness t is
                                                      s
                                                0.615
                                           t fb
                                              5       5 0.31 in
                                           2      2
                                          3
                    Use a stiffener at least  / in thick.
                                           8
                      The minimum stiffener length l is
                                                   s
                                                14.2
                                      d c
                                         2 t 5       2 0.78 5 6.3 in
                                            fc
                                       2          2
                      The minimum length is for a “half depth” stiffener, which is not pos-
                    sible in this example because of the weak axis connections. Therefore,
                                                1
                    use a full-depth stiffener of 12 / in length.
                                                 2
                      A final stiffener size check is a plate buckling check that requires
                    that
                                             Ws    6.5
                                         t $     5     5 0.433 in
                                          s
                                              15    15
                                                                1
                      Therefore, the minimum stiffener thickness is  / in. The final stiffener
                                                                 2
                                                      1
                                                 1
                                                             1
                    size for the strong axis beam is  /   6 /   12 / . The contact area of this
                                                  2    2      2
                    stiffener against the inside of the column flange is 6.5   0.75   5.75 due
                    to the snip to clear the column web to flange fillet. The stiffener design
                    strength is thus 0.9   36   5.75   0.5   93.2 kips > 29 kips, ok.
                      Welds of stiffeners to column flange and web. Putting aside for the moment
                    that the weak axis moment connections still need to be considered and
                    will affect both the strong axis connection stiffeners and welds, the