Page 281 - Industrial Power Engineering and Applications Handbook
P. 281

11/260  Industrial Power Engineering and Applications Handbook
        Table 11.4  Test voltages for conducting dielectric tests
        Motor size and raring       Test voltage (xm.s.)            Examp le

           Stator windings
           (i)  LT motors < 1 kW and rated   500 v + 2vr
              voltage (V,) < 100 V
           (ii)  All sizes and ratings of  motors  1000 V+ 2V,(minimum  1500 V)   (a)  For 220 V motors, the test voltage
                                                                        = 1000 + 2 x220, Le. minimum 1500 V
                                                                    (b)  For 11 kV motors, the test voltage
                                    (Same as col. 5 Table 11.6)         = 1 + 2 x 11 = 23 kV.
           Rotor windings (for wound
           motors)
           (i)  Non-reversing motors   IOOOV + 2 RV                 RV = rated open circuit standstill voltage
           (ii)  Motors suitable for reversing   1000 V + 4 RV          across the slip-rings
              duty or braking during running
              by reversing the UC supply
           If high-voltage test needs be   At 80% of the above
           repated at site during
           commissioning
           Completely rewound windings   Full test voltage as for S  Nos 1 and 2
           Partially rewound windings   75% of the test voltage as for S  Nos  1 and 2
           Overhauled machines      lSV, minimum being lo00 V
        Based on IEC 60034-1

        and above and ratings  lo00 h.p.  and above, during the   insulation of such coils cannot be altered after they have
        course of manufacture of resin-rich formed coils.  For   been inserted into the slots. However, the test is carried
        details on tan  6, see Section 9.6.1 and Figures 9.1 and   out on a completed identical machine to establish reference
        9.8. This is mainly an in-house stage inspection for such   data for field tests. Random sample testing is, however,
        coils. It is conducted on each individual coil, during the   possible with two identical coils placed in the slots. The
        course of manufacture, to check for adequate insulation   test sample of slots can also be made. For more details
        impregnation and quality of insulation, before insertion   see Section 9.6 and IEC 60894.
        into the stator slots. The same process  would apply  to
        the  rotor  slots of  a  wound  rotor  when  the  rotor  open   Method of measurement and acceptance norms
        circuit voltage is a minimum of 5 kV, which is rare. This
        is  commonly  known  as  the  dielectric loss  factor  or   A Schering bridge* or an equivalent type  of bridge is
        dissipation  factor  of  a  motor  winding  coil  and  is  the   used  to determine the  values of  loss factors tan  6 and
        basic measure of the condition of the insulation to ground.   A tan 6, i.e. the increase in tan 6values with the voltage.
        It also gives an idea of ageing or the general condition of   A graph is then plotted between the behaviour  of tan 6
        the insulation. With the help of this data, the  processing   with the  applied  voltage as shown in Figure  9.8. This
        quality of the insulation of the coils can be easily monitored   graph also provides basic reference data for field checks
        as well  as the  condition of  the insulation between  the   before the motor is energized.
        conductor laminations, the inter-turn insulation and the   The loss tangent should be measured on the samples
        insulation  of  the  end  windings  (over-hangs)  etc.  This   at room temperature  at voltages varying  from 20%  to
        factor is also useful in determining the insulation condition
        of each slot of the stator or the rotor.       *The basic principle of these methods is to charge a capacitor up to
          To  carry  out this  test  on  a  wound  machine  (post-   the  specified test  voltage and then  discharge it  through the coil
        impregnated) would  be pointless  as the  quality  of  the   under test.




        I              2               3                          4               5
        tan  60.2,            + (tan 60.6,  - tan  60.v,)                (A tan 6 - per step of 0.2VJ
        100% samples   95% samples     Remaining 5% samples       95% samples     Remaining 5% samples
        30 x           2.5 x 1r3       3 x IO-’                   5 x 10-3        6 x
        Note  If more than 5% of the samples show test results in the range of columns 2 and 3, or between columns 4 and 5,  the test can be
        regarded as satisfactory. Otherwise the test can be continued with an equal number of further samples, if necessary, even up to the total
        number of bars or coil sides.
   276   277   278   279   280   281   282   283   284   285   286