Page 285 - Industrial Power Engineering and Applications Handbook
P. 285

11/264  Industrial Power Engineering and Applications Handbook
         exceed  the  permissible  value  for  a  given  class  of   dynamometer  or other  methods  it  may  be  accurately
         insulation.                                  determined as follows:
                                                              974
       The readings at any point should be taken within 6 seconds   Torque = - 0.9 x (input in kW - Stator 1; R1  loss)
                                                                  x
       for motors of output 7.5 kW and below  and  10 seconds   Ns
       for motors above 7.5 kW.                       The factor 0.9 accounts for a 10% reduction in the torque
                                                      as an arbitrary allowance for harmonic losses.
       Measurement of starting torque, pull-out torque   When the torque is determined by the above method,
        and pull-in torque                            the voltage during the test should be so adjusted that the
                                                      locked rotor current  is approximately  equal to the full
        Any of the methods described in Section 11.4.5 may be   load current. After the locked rotor test, the resistance of
        adopted to measure the torques  developed. The torque   the stator windings should be measured and may also be
        should be measured with the rotor in various positions,   considered for calculating the 12R losses.
        wherever possible. The minimum value should be taken
        as  the  starting torque.  Readings  of  voltage,  current,   11.5.2  Open-circuit voltage ratio test for slip-
        frequency and power input will also be taken. The starting   ring motors
        torque  and  starting current  may  be extrapolated  when
        the test is carried out at a reduced voltage. For extrapolation   In  slip-ring  motors  normal  voltage  and  frequency  are
        of  the  test  results  at  rated  voltage  the  test  must  be   applied  to the  stator  with  the  connection  of  the  rotor
        performed  at least  at three  test  voltages.  At  each  test   brush  gear open-circuited.  The phase voltages induced
        voltage, readings of voltage, current, torque,  frequency   in the rotor are then measured across the slip-rings.
        and power input must be taken. The values  of  starting
        current and starting torque may then be extrapolated from   11.5.3  Verification of degree of protection
        these curves.  The effect of  magnetic  saturation  is  not
        considered in this test method.               We have defined the various types of enclosures adopted
                                                      by various manufacturers to suit different locations and
                                                       environmental conditions in Tables 1.10 and 1.11. Here
        Alternate method                               we briefly discuss methods for testing these enclosures
        When the locked rotor torque cannot be measured by the   to check  their  compliance  with  defined  requirements.

        Table 11.7  Protection against contact with live or  moving parts

        First characteristic  Test requirements
        number
        0             No test is required
        1             The test is carried out with a sphere of SO mm diameter. The sphere should not touch live or moving parts inside the
                      enclosure.
        2             (a) Finger test
                      In LT motors, a standard test finger as shown in Figure 11.7 is used, connected by an incandescent lamp to one pole
                      of a supply of at least 40 V, the other pole of the supply being connected to the parts intended to be live in normal
                      service. All parts must be connected electrically. The lamp should not glow when an attempt is made to touch the bare
                      live parts or insufficiently insulated parts. Insufficiently insulated parts may be covered with a metal foil connected
                      to those parts that are live in normal service. Conducting parts covered with varnish or enamel only or protected by
                      oxidation or by a similar process may be considered as insufficiently insulated. In HT motors, the clearance is verified
                      with the minimum clearance required to withstand the dielectric test as in Section 11.4.8.
                      (b) Sphere test
                      The enclosure should not permit a ball of  12 mm diameter to enter the enclosure.
        3             The test is carried out with a steel wire of 2.5 mm diameter. The wire should not go through the enclosure.
        4             The test is carried out with a steel wire of  1 mm diameter. The wire should not go through the enclosure.
        5             The test is carried out by using an apparatus shown in Figure 11.8, consisting of a closed test chamber in which talcum
                      powder can pass through a sieve having square openings of 75 pm, and is held in suspension by an air current. The
                      amount of talcum powder is supplied at 2 kg per cubic metre size of the test chamber. The enclosure under test is
                      placed inside the chamber and is connected to a vacuum pump which maintains, inside the enclosure, a differential
                      pressure equivalent to not more than a 200 mm column of water.
                      The test is stopped at the end of two hours if the volume of the air drawn in during this period is from 80 to 120 times
                      the volume of air in the enclosure under test.
                      If, with a vacuum equivalent to a 200 mm column of water, it is not possible to draw air 80 times the volume of the
                      enclosure under test, the test must be continued until the value is attained. In no case must the test be carried out for
                      more than 8 hours.
                      The permissible amount of talcum powder penetrating the enclosure should not affect operation of the equipment.
        6             The test is similar as for number S  but now  no deposit of dust should be observed at the end of the test.
   280   281   282   283   284   285   286   287   288   289   290