Page 284 - Industrial Power Engineering and Applications Handbook
P. 284

Philosophy of quality systems and testing of electrical machines  11/263
             kinds normally appear on the first or the entrance   subtracting  the  primary  copper  loss  (ZitRl) at  the
             coil of the winding.                       temperature of the test from the input watts. If the values
         2  In practice, voltage surges can be of various  shapes   of  current  and power  are recorded,  from  about  130%
            (Figure 17.2) and may even be so steep as to have a   normal voltage downwards, and a graph of power against
           front time as low as  0.2 ps or less. For the purpose of   voltage  plotted,  the  core loss can be  separated,  from
           the impulse test, however, only a standard lightning   friction and windage losses.
           impulse, as defined by  1.2/50 (Section  17.6) can be   Interception with the zero voltage axis, which represents
           considered.                                  friction and windage losses, may be found by plotting a
         3  The impulse level in column 4 of Table 11.6 has been   second graph with the square of the voltage as the abscissa
            so chosen  that  the  machine  winding  will  have  a   and the watts as the ordinate (Figure 11.6),
            sufficiently  high level of insulation to fit into the system
           of  insulation  coordination,  as discussed  in  Section   11.5.1  Locked rotor test
            17.11 and Table 11.6.
         4  The test on a  sample coil  at 50% test  voltage will   This test is conducted by supplying the stator windings
           indirectly represent the test on the whole machine, in   with the rotor in the locked condition. In slip-ring motors,
           that the sample coil is tested under almost the same   the rotor windings  are also short-circuited.  The test is
           conditions to which the whole machine would have   carried  out to determine the  soundness of  the rotor in
           been subjected when applied with the full test voltage   squirrel cage motors, and to measure the starting current,
           of column 4 of Table  11.6.                  power factor, starting torque and impedance. It also enables
         5  Quantum of  impulse voltage.  There  is  no  agreed   us to draw a circle diagram, for single squirrel cage rotor
           calculation to determine the severity of impulse that   motors and wound rotor motors. This test may be carried
           must be applied to these two sample entrance coils as   out at a reduced voltage that will produce the rated current
           this  varies  from  one machine  to  another  and  other   of the motor. The locked  rotor torque  test is not to be
           factors such as:                             performed on a wound rotor motor. The starting torque
           - Rise time tl (Figure  17.3) of the voltage impulse   in a wound motor has no relevance, as it can be varied as
           - Length of the entrance coil, and           desired.  The locked rotor current test is carried out on
           - Number of turns.                           both squirrel cage and wound rotor motors. It should be
           As discussed in Section 17.8 the bulk of the voltage   recognized that testing induction motors  in the locked
           of  a fast-rising impulse wave  applied  to the whole   rotor condition involves unusual mechanical stresses and
           winding will appear across the entrance turns.  This   a high rate of heating. Therefore, it is necessary that:
           may vary from 40% to 90%, depending on the steepness
           of the wave front. Report TC-2 of IEC 60034-15 has   The direction of rotation be established prior to this
           recommended  a value  of  50% as adequate to meet   test.
           general  requirements.  However,  this  value  may  be   The mechanical method of locking the rotors must be
           finally decided by the manufacturer of the machine   strong enough to prevent injury to nearby personnel or
           in consultation with the end user, based on the surge-   damage to equipment.
           generating source (interrupting device), its likely front   As the windings  are heated  rapidly, the test  voltage
           time, the type of machine and its exposure to external   must be applied as quickly as possible. Care should be
           surge-generating sources.                     taken to ensure that the motor temperature does not


         11.5  No load test

         The no-load test is a very informative method to determine
         the no-load current, core* and pulsationt losses, friction
         and  windage  losses,  magnetizing  current  and  the  no-
         load  power  factor.  The test  also reveals mechanical
         imbalance, if any, performance of the bearings, vibration
         and noise level of the motor.
           The motor is run on no load at a rated frequency and
         voltage, until the watts input becomes constant (to ensure
         that the correct value of friction loss is obtained). Readings
         of line voltage, current, frequency and power input are
         taken.
           The watts input is the sum of the friction and windage
         losses, core loss and no-load primary loss  (I:,&).  The
         sum of friction, windage and core losses is obtained by             windage losses 4
                                                                              Friction and
         *Core loss is the magnetizing or hysteresis loss and represents the
         iron loss of the machine.
         'Pulsation  loss is the harmonic loss of the machine.   Figure 11.6  No-load curves to separate out no-load losses
   279   280   281   282   283   284   285   286   287   288   289