Page 283 - Industrial Power Engineering and Applications Handbook
P. 283

11/262  Industrial Power Engineering and Applications Handbook
       interrupting  device  has  multiple  re-strikes  during  a   15
       switching  operation,  or  at  locations  expected to  have
       surges higher than normal due to transferences, such as
       at a power generating station.  For all these conditions,  t  lo
       higher values of impulse levels, as in column 3 of Table   2  5
       11.6, may be chosen or surge suppressors installed.   Ql
                                                      so
                                                      0,
                                                      P
       Test recommendations                           D
                                                      2  -5
        1  The test coils should be finally processed  and then   8
          embedded into the slots.                    T  -1 0
       2  The  number  of  sample  coils  must  be  two  unless
          changed deliberately.                         -1  5
       3  All coils that are subjected to this test must fulfil the   0   0.1   0.2   0.3  0.4   0.5   0.6  0.7   0.8
          test requirements. In the case of a failure, investigations   Time (milliseconds) +
          must  be  carried  out  to  establish  the  cause  and  the
          same rectified before undertaking the insulating process   Figure 11.4  Voltage traces of  a satisfactory coil (without
          on the next batch of coils.                 interturn fault)

        Test procedure
                                                         20
        1  For inter-turn insulation
            The test should be performed by applying the voltage
            between the two terminals of the sample coils.
            The inter-turn  test  voltage  must  be  generated  by  T  lo
            damped oscillating discharge of capacitors or with   5
            the help of a high-voltage generator to pulse a fast-   go
            fronted damped oscillating voltage wave. In order   B  ....
                                                       P
            to obtain an even distribution of the impulse between   D
            the  coil  turns,  the  front  time  of  the  first  voltage   2 -10
                                                       2
            peak  must  not  be  below  0.5  ,us.  The  resultant   T
            waveform produced  by the coil, is displayed on a
            storage  oscilloscope,  and  can  be  compared  with   -20
            the waveform of a known good coil. Figures  11.4   0   0.1   0.2   0.3  0.4   0.5   0.6  0.7   0.8
            and 11.5 show a clear difference in the waveforms         Time (milliseconds)-
            between a good and a defective coil.
            The  voltage  peaks  between  the  terminals  of  the   Figure 11.5  Voltage traces of an unsatisfactory coil (with
            sample coils should be 50% of the value given in   interturn fault)
            column 4 of Table 11.6, i.e. '/2(4Vr + 5) kV.
        2  For main insulation (ground and inter-turn insulation
          withstand test)                                  be applied between the coil terminals and the ground.
          Any of the following methods can be adopted:     The number of impulses should be 5, unless agreed
            Power frequency voltage test                  otherwise by the manufacturer and the user.
            - The HV test should be performed first by applying
              r.m.s. value (2Vr + 1) kV for one minute, as shown   11.4.10 Principal considerations in framing the
              in Table 11.4 between coil terminals and ground.   specification for impulse voltage
              Then the applied voltage should be increased at   withstand level and underlying the test
              1  kV/s  up to  2(2Vr + 1) kV,  and then  reduced
              instantly at least at 1  kV/s to zero. If there is no   procedures
              failure, the test will be considered as successful,   1  When a steep-fronted voltage surge occurs between
              fulfilling the requirement of column 4, of Table   one  terminal  of  the  machine  and  the  ground  the
              11.6. This procedure would give a test voltage   corresponding  phase  does  not  instantly  (during the
              equivalent to 2 . 4 . (2 V,  + 1) kV, which is even   rise time t, Figure 17.3) adjust to the same potential
              more than the values of column 4, i.e. > (4V, + 5)   at  all  the points  on the  curve.  Hence, two types of
              kV.                                        voltages develop in the machine winding, i.e.
            - A  d.c. test  is also permitted  by  IEC 60034-15.   Voltage between copper and ground, which can be
              The d.c. voltage should be at least  1.7 times the   called the transverse voltage, and the voltage along
              peak of the power frequenc  routine test voltage,   the  copper  which  can  be  called  as  longitudinal
              i.e.  a minimum of  1.7  x  % 7 2(2Vr + 1)kV.   voltage.
            Impulse voltage test                           While the transverse voltage stresses the main wall
            The full test voltage of column 4 of Table 11.6, Le.   insulation, the longitudinal voltage stresses the inter-
            a standard lightning impulse of  1.2/50 ps, should   turn insulation. The bulk of the components of both
   278   279   280   281   282   283   284   285   286   287   288