Page 387 - Industrial Power Engineering and Applications Handbook
P. 387

131362 Industrial Power Engineering and Applications  Handbook
        conducting a short-circuit test up to the desired duration   Table  13.12  Derating  for  higher  altitudes  for  metal  enclosed
        of  1 or  3  seconds,  the  short-circuit  current,  although   switchgear assemblies and bus systems
        theoretically asymmetrical until the test period, may be
        regarded as symmetrical (having reached its steady state)   Altitude (mi   ~  Derutitig factors
        after three or four cycles. The content of asymmetry is   LT systems  HT systems 1  Dielectric  strength  Continuous current
        ignored after three or four cycles for all calculations and                   rutirig
        practical  purposes. In  fact, a d.c.  component  less than
        50% that of the peak symmetrical component of the fault,   2000   1000   1 .0   1 .OO
        current Is,,  at  any  instant during the  course  of  short-   2600   1500   ~  0.95   0.99
        circuit  condition may  be  ignored.  In  other words,  the   3900   3000   0.80   0.96
        relevance of the asymmetry may be considered only up   Notes   I  Intermediate  values may be obtained by  interpolation.
        to the first peak, as the immediate subsequent peaks may   2  No derating i,  applicable in case of insulated switchgear
        also be less than 50% of the peak value of Is,  (Idc < 0.5   (GIS) assemblies.
        ZM) at that instant.                           Source  ANSI C-37.20.2 and C-37.23
          The generation of  an asymmetrical current on an a.c.
        system, leads to the inference that a short-circuit condition   increasing the clearances and the creepage distances to
        will  give rise to  a  d.c. component due to a shift in  its   ground and between phases as discussed in Section 28.5.2
        zero axis. During the sub-transient state the value of the   and Tables 28.4 and 28.5.
        asymmetrical  current  will  be  the  phasor  sum  of  the   To achieve the original value of the continuous current,
        symmetrical  Is,  and  the  asymmetrical  Idc, current   the size of the current-carrying components may also be
        components. For details refer to Section  14.3.6.   increased  to  carry  the  higher  amount  of  current  in
                                                       proportion to the derating.
        13.4.2 Service conditions
                                                       Atmospheric  conditions
        Ambient temperature, altitude and atmospheric conditions   A  normal  enclosure  is  meant  for  a  reasonably  clean
        at the place  of  installation  of  electrical equipment  are   atmosphere and a relative humidity not more than SO%
        considered to be the service conditions for the equipment   for LT and 95%  for HT indoor  enclosures. Where the
        to operate and perform its duties. All electrical equipment   atmosphere is  laden  with fumes or steam, saline or oil
        is designed for specific service conditions and variations   vapours, heat and humidity, excessive dust and water or
        may  influence its performance.  Below  we analyse the   contaminated  with  explosive and fire hazardous gases,
        influence of such non-standard service conditions on the   vapours  or  volatile  liquids  (Section  7.11)  a  special
        performance of  equipment and the required safeguards   enclosure with a higher degree of protection  is required
        to achieve its required performance.
                                                       as in  IEC  60529 or IEC 60079-14.  For non-hazardous
                                                       areas, the enclosure can be generally one of those discussed
        Ambient temperature                            in Tables 1.10 and 1. I 1, and when required can be provided
                                                       with  special  treatment  to  the  metallic  surfaces.  For
        The rating of an indoor or outdoor switchgear assembly   hazardous  areas,  however,  special  enclosures  will  be
         is referred to at an ambient temperature of 40°C. For a   essential as discussed in Section 7.11.
        higher ambient temperature  the rating of  the assembly   In outdoor type switchgear or controlgear assemblies
         will be reduced in the same proportion as for the busbar   the normal  practice  is  to provide  a  double door  in  the
         systems and as shown in Table 28.3.
                                                       front to house the front panel and protect the door knobs,
                                                       meters, lights, pushbuttons, reset  knobs or other acces-
        Altitude                                       sories  mounted  on the door  and thus prevenl  water or
                                                       dust leaking through joints, knockouts and fitments etc.
                                                       It  is also recommended to have a canopy on the top of
         For assemblies using  the surrounding  air as the   the enclosure to protect the panel from direct rain. Figures
         insulation and  cooling medium                13.6 and  13.28 illustrate this type of  construction.
         The standard altitude for an LT switchgear assembly is
         2000 m and for HT  1000 m, as in ANSI-C-37.20C and   Flame- or explosion-proof assemblies (Type Ex. d)
         IEC 60439-1. At altitudes higher  than this, the normal
         increase  in  temperature  will  become  greater  and  the   For  hazardous  areas  flameproof  enclosures  alone  are
         dielectric strength less for all assemblies using air as the   recommended, except in  areas with moderate  intensity
         insulating and cooling medium. For applications at higher   of contamination and where such assemblies are located
         altitudes, therefore, the derating factors as noted in Table   away  from  the  affected  area  and  in  a  separate  well-
         13.12 must  be  applied  to  obtain  the  reduced  level  of   ventilated room, when  pressurized enclosures may also
         dielectric  strength,  i.e.  one-minute power  frequency   be safe. The reason for this precaution  is that frequent
         voltage  withstand,  impulse  voltage  withstand  and  the   arcing takes place within the enclosure on each switching
         continuous current rating etc. to which level the switchgear   of a contactor, switch, breaker or an OCR etc. and also
         assembly will now be rendered to. To achieve the original   during operation of power and auxiliary contactors.
         level of dielectric strength, the insulation system of the   The classification of gases, vapour and volatile liquids
         switchgear assembly will  have  to be  improved  by  the   according to their ignition temperatures has been given
         same degree  as  the  derating. This  can  be  achieved by   in Table 7.4. The basic requirements of these enclosures,
   382   383   384   385   386   387   388   389   390   391   392