Page 390 - Industrial Power Engineering and Applications Handbook
P. 390

Switchgear  and controlgear assemblies  13/365
        before the actual tripping. When the tripping is electrical   I,,  = system fault level
        it may involve a trip coil and a motor mechanism adding   t,,  = pre-arcing time of the HRC fuses or tripping time
        10  the mechanical tripping time, actuating time of relays,   of  MCCBs or MCBs,  which  would be  much  less
        minimum  time  of  tripping  of  interrupter  itself  (Table   than S ms (less than one quarter of a cycle for a50
         19.  I  and some safety margins. While the actual tripping   Hz system; see Figure  12.18 for more  clarity)
        time may  still be quite low, it is customary to design a
        system for one or three seconds and for which is designed   then the let-out energy of  the current limiter,
        all  the  equipment.  devices  and  components,  protected   I,:
        by  such a device.                                   ' t,,
          The value of short-time rating   . t,')  of the system   If I,  is the equivalent  I -second fault current
        may  now  exceed,  the  thermal  rating  of  some of  the
        equipment,  devices  and  components,  i.e.  I   then  I,'  . 1 = 13  . t,,
        thermal  rating.  This condition  may  be  more  I
        smaller ratings, particularly 600 A and less (such as for   or   I, = I,, vFi
        busbars), than larger onec. At higher currents, the natural
        thermal  rating  itself, due to  the  higher  cross-sectional   Since tSc will be too low  (< 5  ms for a 50 Hz system)
        area.  will  become  higher  than  the  required  short-time   I, will  be  much  less than 7% of I,,  in all situations. To
        rating. The short-time rating will remain  the same for a   assign a short-time rating  to the  protected  devices and
        particular fault level of a system, irrespective of the current   components in such cases is therefore of little relevance.
        rating  of  the  circuit. For  more details  refer  to  Section   As noted above, current is the cause of heat, for which is
        28.4.1. Whenever the short-time rating exceeds the thermal   assigned the thermal duty of  a current-carrying device.
        rating.  a larger area of cross-section of the main busbar   component or part. Also note the following:
        system and  the other current-carrying components will
        become necessary.                                Current limiting devices need not be protected.  since
          Figure  13.29 illustrates a  simple distribution  system   they  are  already  very  fast  acting  and,  hence,  self-
        and location of the main buses, devices and components   protected.
        to  define  the  current  ratings  of  all  such  devices  and   But  they  are also rated  for the  same fault level  for
        components  under  different  operating  conditions. The   which the system is designed  as they  are connected
        ideal  current ratings  of  these  components are given  in   directly to the  system. This is a safety requirement.
        Table  13.13 for an easy illustration.           Similarly, in a draw-out switchgear assembly. the I/C
          The fault currents also develop electrodynamic forces,   and O/G power contacts of a module and its mounts
        F,,,. as in  equation  (28.4) due to the  sub-transient  d.c.   (insulators and supports) being already protected may
        component. These forces play  an  important role  in the   be suitable only for the thermal rating of their feeders.
        mechanical design of the interrupting device, the  load-   When such devices are used at more than one location
        bearing and mounting structures for the interrupter and   in  a  circuit,  their  ratings  must  be  meticulously
        the  bus  system, and the hardware  used  in a switchgear   coordinated  to ensure  isolation  of  the faulty  circuit
        assembly. All  such  mechanical  parts,  supports  and   alone. Refer to Section  12.4.2 and Figure  12.1 1  for
        hardware  should  be  adequate to  withstand  such forces   more clarity.
        when they arise. A procedure to arrive at the ideal size of   A  current-carrying  device  or  component  in  a
        the current-carrying components, mounting structure, type   distribution  network  may  be  subjected  to  varying
        of  supports  and  hardware  etc. is  discussed  in  detail in   degree  of  electrodynamic  stresses,  depending  upon
        Example 28.12.                                   its location with reference to the  network. Referring
          If  the  short-time  rating of the  interrupting  device  is   to Figure  13.29, the circuits away from the source of
        higher  than  the fault  level of  the  system, which  is  the   supply are subjected to lower stresses than the circuits
        case with modern interrupting devices, the fault level of   nearer  to  it.  Accordingly, the  coordination  is  done
        the system alone will prevail for the busbars, components   between the protective devices, used in the upper and
        and hardware.  For example. for a system fault level of   lower streams of circuits, to ensure that only the faulty
        50 kA,  if  the  interrupter  used  is  of  65  kA  short-time   circuit is isolated, rather than  isolating other circuits
        rating,  the  bus  system  and  all  associated  components   in the upper stream (Section  12.4.1).
        will be designed for SO kA only.

        Current limiting type                          Notes on  Table  13.13
                                                         An isolator, such as at locations C, and C2 in Figure
        Examples are HRC fuses (both LT and HT) and MCCBs   13.29, may  sometimes be used to isolate the circuits
        and MCBs (LT only). which are available with current   it  is  feeding,  say,  for  maintenance  or  repair\.  This
        limiting features and are in  extensive use. The tripping   isolator is simply a switch and provides no protection
        time  of  these  devices is extremely  low and much less   to the circuits. For a fault on the outgoing  side, the
        than one half of a cycle of the current wave. They therefore   individual  outgoing  feeders  must  have  their  own
        do not  allow the  fault current to rise to its prospective   protection. For a severe fault elsewhere in the system,
        peak. The protected devices and components can thus be   there must be a protective feeder closeby, in the upper
        selected based on the let-out energy of such devices on   stream.
        fault. which is extremely low, than the fault level  of the   Role of an OCR: this is only an overcurrent protection
        systcm. If                                       device and does not provide short-circuit protection.
   385   386   387   388   389   390   391   392   393   394   395