Page 389 - Industrial Power Engineering and Applications Handbook
P. 389

13/364 Industrial Power Engineering and Applications Handbook
        Note                                            cross-sectional area of the current-carrying components.
        One may observe that all the above special  service conditions are   To determine the cross-sectional  area for this short-
        generally the same as for the rotating machines discussed in Section   time rating and decide the mounting structure, supports
        1.6.                                            and hardware etc. for the busbars, a brief procedure is
                                                        described in Example 28.12.
                                                          Both ratings, thermal and short-time, will define the
        13.5  Deciding the ratings of current-          cross-sectional area of the current-carrying components.
              carrying equipment, devices               The more severe of  the two will  then prevail. In  the
              and components                            following text we explain the procedure to assign the
                                                        short-time current rating to equipment, a device or a
                                                        component.
        The  rating  of  current-carrying  equipment  (switchgear
        assemblies, such as for the main  bus  system), devices
        (breakers, switches and  contactors) and  components   13.5.1 Assigning a short-time rating
        (connecting  links  and  wiring  etc.)  is  defined  by  two   The bus system of a switchgear assembly, its interconnec-
        parameters:                                    ting links and wires are the protected type components,
                                                       whereas an  interrupter  (breaker, switch or a fuse) may
           Thermal rating or continuous current rating  This   be a protecting or protected type, depending upon their
          takes account of heat losses ( = I;  . t, t being the time   application and location in the circuit. A contactor and
          to reach thermal equilibrium). as generated during a   an  OCR  are  therefore  protected  devices  in  the  same
          long continuous operation under rated conditions. In   context.  for they  provide  no  short-time  protection.  A
          breakers, switches and contactors, it will also define   protecting device may become protected when  it is also
          their duty cycle, i.e. the type of duty they may have to   provided with a back-up protection.
          perform (Section  12.10 and Table  12.5).      A  breaker, usually  an MCCB or an MCB on an  LT
            To  the  basic  current  requirement  is  applied  the   system,  can  be  provided  with  backup  HRC  fuses to
           derating factors for various service conditions, as noted   enhance their short-time rating. This may be done when the
           in  Section  13.4.2.  The  equipment,  devices  and   available MCCBs or MCBs possess a lower short-time
           components may then be chosen to be as close (nearest   rating than the fault level of the circuit they are required
           higher) to this rating  as possible from the available   to protect, and make them suitable for the fault level of
           standard ratings. Based on these ratings, the minimum   the  circuit.  But this  is not  a  preferred  practice  and  is
           cross-sectional areas of the other current-carrying parts   seldom  used.  As  a  rule  of  thumb,  the  device  that  is
           used in the circuit. such as interconnecting links and   protecting must be suitable to withstand electrically and
           the cables-are calculated.                  endure mechanically the system fault current for a duration
                                                       of one or three seconds, according to the system design.
          Short-time rating  This will  define           The duration,  however, is  no criterion  for a  current
                                                       limiting type protecting device, and a protected equipment,
          The electrical rating on a fault or short-term high current   device  or  component  can  have  a  short-time  rating
          thermal effects, expressed by a I& . tsc , i.e., short-circuit   commensurate  with  the  tripping  characteristics  of  the
          current (Isc) and its duration (tSC-  1  or 3 seconds).   protecting  interrupter. Accordingly  these  two  types of
          The mechanical endurance of the current-carrying  parts   tripping characteristics are explained below.
          of  all  the  equipment,  bus  system,  devices  and
          components, used in a particular circuit as well as the   Delay tripping
          load-bearing members and supports on which they are
          mounted. The electrical parts  of  a  device (breakers   The breakers (OCBs, MOCBs, ABCBs, SF6 and VCBs)
          and  switches,  etc.)  are  the  responsibility  of  the   for HT and ACBs and MCCBs* for LT systems are devices
          component  manufacturers.  The  manufacturer  of  the   that have a tripping time of more than a cycle on fault.
          switchgear  assembly  is  responsible  for  the  busbar   The tripping time can vary from 1 cycle (20 ms) to 5-6
          systems, metallic links and wires.           cycles (100-1 20 ms for 50 Hz systems), depending upon
            The mechanical  requirements  of  the  load-bearing   the type of  interrupter  as discussed in  Chapter  19 and
          members, supports, busbars and metallic links in the   noted in Table  19.  I.
          incoming circuit will depend upon the electrodynamic   This time allows the fault current to reach its peak and
          forces arising out of the first major peak of the fault   therefore  all  the  equipment,  devices  and  components
          current,  as discussed  in  Section 28.4.2.  This is  not,   protected by  such a device must be suitable for the full
          however, applicable to devices that are current limiting   fault level of the system. While the tripping time is usually
          as  well  as  the  circuits  and  its  components  that  are   in  milliseconds the duration of  fault, tSC. is considered
          protected by it. These devices isolate the faulty circuit   as one or three seconds. The longer duration than necessary
          long before the fault current reaches  its first highest   is to account for the various time lapses that may occur
          peak. Yet the short-time rating for the incoming circuit
          (as  the  outgoing  circuits  may  not  experience  these
          faults),  should be  selected  from the  standard  short-   *MCCBs
                                                       (i) When they  are normal  duty as considered here.
          time ratings only, as defined in Tables 13.7 and 13.10.   (ii) They  are  also  available  in  the  current  limiting  type.  When
          For this short-time rating is then calculated the minimum   current limiting.  they will not fall into this category.
   384   385   386   387   388   389   390   391   392   393   394