Page 392 - Industrial Power Engineering and Applications Handbook
P. 392

Components
                           <                           Interrupting devices                    >  1  -Equipment    and components A
                                                                            Application
                          When used as a protective device   When used as a protected device   When used as an   As protected parts
                          (as incomer)                   'as outgoing)'             isolator (as incomer)

           Parameters     Tripping time   Tripping time   Tripping time   Tripping time            Interrupter tripping time > 1   Interrupter tripping  time
                          > 1 cycle       < half cycle   > 1 cycle     < 1/2 cycle                 cycle               < half cycle
           (1)            (2)             (3)            (4)           (5)                         (7)                 (8)
           Type of devices   OCBs", ACBs,   MCCBs,       As in column 2   As in column 3   Switching device   Main bus, its feeding tap-offs   All outgoing
                          MCCBs in LT and   MCBs in LT and HRC                      locations  C, and  Cz, as  and interconnecting links or   connections by  solid
                          MOCBS~          fuses in both LT                          Fhown in Figure 13.29   cables etc. and all outgoing   links or cables
                          ABCBsb, SF,  and   and HT                                                links, interconnecting devices
                          VCBs in HT                                                               that are also connected on the
                                                                                                   main bus such as shown at
                                                                                                   section F, Figure  13.29.
           1,  Short-time rating                         I,,,   if connected on the main bus, otherwise  Depending upon the   No relevance
            or symmetrical                               < Isc  depending upon the circuit impedance  protective feeder on the
            fault level   I,,                                                       upstream. Refer to
                                                                                    Figure  13.29
           2  Duration of fault   1 or 3 secondsd   <half cycle or   1 or 3 secondsd   < 1/2 cycle or   I  or 3 secondsd   1 or 3 secondsd   -
                                          < 5 ms for a                 < 5 ms for a 50 Hz
                        t5'
                                          50 Hz system                 system
                                                                                                  I-
                                                                       -
           3  Making capacity  I,  As in Table  13.1 I   As in Table  13. I1        As in Table 13.1 1
                                          -
           4  Endurance of   According  to               As in column (2)   -       As in column (2)   As in column (2)   No additional
             supporting and   electrodynamic forces,                                                                   reinforcement of
             mounting structure,   F,,  = I;  equation                                                                 members or supports
             load-bearing                                                                                              necessary
             members and   (28.4)
             hardware
           5  Cross-sectional  area   Taken care of by the manufacturer of the devices             (a)  For  mechanical  endurance  As per maximum
             of current-carrying                                                                     a~cordingtoF~(Section28.4.2) thermal rating of the
             metallic links or                                                                     (b) For  electrical  endurance  feeder.
             cables                                                                                   ~rl: I,, (Section28.4.l)and
                                                                                                   (c)  For maximum thermal rating
                                                                                                     =  I:t  of the feeder,
                                                                                                     whichever is higher of b and
                                                                                                     c. (I = time required to reach
                                                                                                     the thermal eauilibrium)
           Figure 13.29 illustrates  a typical power distribution scheme to assign ratings to the various devices, components and husbar systems.
           Wse of these breakers is gradually  waning in the light of more advanced technologies available in an ACB and MCCB.
           bUse of these breakers is also waning  in  the light of more advanced technologies available in SF,  and VCBs (Section 19.5).
           'These  protect the circuits in the lower stream and are protected  by a device in the upper stream such as feeders D and E in Figure 13.29.
           dNormally only a I-second system is in use. The 3-second  system is severe, for which protective devices in certain ratings may not be possible or may become  prohibitively  costlier to produce.  The 3-second system
            may, however, be used for a generator circuit to protect the generating source from a fallout on a fault elsewhere in the system.