Page 483 - Industrial Power Engineering and Applications Handbook
        P. 483
     Instrument and control transformers: application and selection  151457
         15.1  introduction                            associated with the same power system and interrupting
                                                       devices as a switchgear assembly, they should generally
                                                       meet the requirements for a switchgear assembly. except
         Transformers are used in an auxiliary circuit, linked to a   for small variations in  the test requirements.  For more
         power circuit, to indicate, measure and control its voltages   details refer to the following publications:
         and currents. They find application in a switchgear or a
         controlgear  assembly  and  a  switchyard.  It  would  be
         impracticable  to  produce  indicating  and  measuring   1  For voltage transformers
         instruments or protective devices to operate at high  to   IEC  60044-2  and  IEC  60186  (for two-winding
         very  high voltages  or currents. The universal  practice,   transformers such as CVTs)
         therefore, is to transform the high voltages, say, 415 V   2  For current transformers
         and above. and currents above 50 A to reasonably  low   IEC 60044- 1  and IEC 60044-6
         values, as discussed later, for these applications. Indicating
         and  measuring  instruments  and  protective  devices  are   SECTION I: VOLTAGE
         designed for these reduced values. The transformers used
         to transform voltages are known as voltage transformers*   TRANSFORMERS
         and those to transform currents as current transformers.
         Below we discuss their classifications, basic requirements   15.4 General specifications and
         and design parameters.
                                                             design considerations for
                                                             voltage transformers (VTs)
         15.2  Types of transformer
                                                       These transformers develop a voltage on the secondary.
         15.2.1  Voltage transformers (VTs)            substantially proportional to the voltage on the primary
                                                       (there being  no  knee point  saturation. as is  sometimes
         The\e may be classified as follows:           required in CTs (Section 15.6.l(viii)).
         I  Instrument voltage tramformers             15.4.1  Instrument voltage transformers
            (i) Conventional  two-winding,  electromagnetic
               voltage transformers
            (ii)  Residual voltage transformers (RVTs) and   1 Rated primun voltage
           (iii)  Capacitor  voltage  transformers  (CVTs).  These   This will generally be the nominal sy\tem voltage, except
               may  be  used  for  metering  or  protection,  with   for transformers connected between a phase and the ground
               very  little  difference between  the two as  noted   or between the neutral and the ground, when the primary
               later.                                  voltage will  be considered  as  I/?  3  times the  nominal
         2  Control transformers                       systems voltage (V,)
         15.2.2  Current transformers (CTs)            2 Rated  secondary voltage
                                                       InEurope and Asian nations this is generally 110 or 1 101
         These may be classified as:                    y;3 V,  (63.5 V) for phase-to-phase or phase-to-ground
                                                       auxiliary circuits respectively. In  @e USA and Canada
         1  Instrument current transformers            these  voltages  are  120 oy_ 120/ % 3  V  for  distribution
            (i) Measuring current transformers         systems and 1 IS or 1 IS/ %'3 V for transmission systems.
            (ii) Protection current transformers and
           (iii) Special-purpose current transformers, class 'PS'.
         2  Interposing current transformers           3 Rated frequeizcx
         3  Summation current transformers             This may be 50 or 60 Hz as the system may require. The
         4  Core balance current transformers  (CBCTs)   permissible  variation  may  be  considered  as  +2%  for
                                                       measuring  as well  as protection  VTs. These limits are
                                                       based  on  the recommended  variations applicable for a
         15.3  Common features of a voltage            switchgear assembly (IEC 60439- 1 ) or an electric motor
               and a current transformer               (Section  1.6.2).
                                                       4 Insulation systems
         15.3.1  Design parameters (service conditions   These  transformers  may  be  PVC  taped.  thermoplastic
               and likely deratings)                   (polypropylene) moulded, fibreglass taped. polyester resin
         The\e are similar to parameters for a switchgear assembly   cast or epoxy resin cast depending upon the system voltage
         as  discussed  in  Section  13.4.  Since  they  are  directly   and the surroundings. HT indoor transformers, for instance,
                                                       are  generally  polyester  or  epoxy  resin  cast,  and  are
                                                       economical  with  good  dielectric  properties.  They  are
         * Potential transformer (PT) is not the appropriate word to identify   resistant to humid, chemically contaminated and hazardous
         an instrument  voltage  transformer.          areas. Outdoor HT transformers, however. may be epoxy





