Page 488 - Industrial Power Engineering and Applications Handbook
P. 488

15/462  Industrial Power Engineering and Applications Handbook
                       R   Y   B                       Healthy system
                       1   1   1                       In this case, all the three phases would be balanced and
                                                       the residual voltage, Ve, will be zero. The three voltage
                                                       phasors in the open delta windings will be as illustrated
                                                       in  Figure  15.5(a). The phasor  sum of  these phasors  is
                                                       zero. Therefore V,  = 0.
                                   =G
                                                       Ground fault on one phase
                                                       System neutral grounded
                                 voltage               Consider a ground fault on phase R. The voltage across
                                                       this phase will become zero and the phasor diagram will
                                                       be as illustrated in Figure 15.5(b). The other two phasors
        Figure 15.4(a)  Connections of a residual voltage transformer   will remain the same as in a healthy system and add to
                                                       give the residual voltage V,,  i.e.
                                                       v,  = JVT'  + v;  + 2.V,VT  cos 120"

                                                       where  VT  is  the  phase  voltage  across  the  secondary
                                                       windings
                                                5
                                                           =2/2v:-vT2=vT
                                                           = 3 x zero phase sequence voltage drop.
                                                       The voltage across open delta is thus the same as the fall
                                                       in the voltage of the faulty phase. It will lead the current
                                                       caused by the ground circuit impedance.

                                                       System neutral isolated
        Figure 15.4(b)  A five-limb transformer to carry unbalanced flux   When the system neutral is isolated, the voltage across
                                                       the faulty phase R will be the same as the ground potential
                                                       and the ground potential will become equal to the phase
                                                       voltage VT as illustrated in Figure  15.5(c). The voltage
        windings. This is due to an open magnetic circuit in the
        secondary  open  delta  winding  having  no  return  path   across the healthy phases  will  become  8VT, i.e.  &
        through the third magnetic limb. This phenomenon does   times more than the normal phase voltage. The phasors
        not exist when three single-phase transformers are used,   V,  and  V,  will thus  be 60" apart  than  120" and  180"
        as  each  transformer  core  winding  will  form  a  closed   from the primary.
        magnetic circuit of its own.
          In a normal three-limb transformer the resultant flux,   .'.  v,  =J(&~T)'+(&~T)*+  2~&v~.&v~~COS60"
        on a  ground  fault, of  the  two  healthy  lines  limb  will
        return through the transformer limb of the grounded line,   = J3v;  + 3v;  + 3v;
        inducing a  heavy  short-circuit current in that  winding.
        This will induce a voltage which will be reflected in the   = 3vT
        corresponding secondary winding, and the voltage across
        the open terminals of the delta will not be a true residual.   i.e. three times the healthy phase voltage.
        This situation is overcome by providing a low reluctance
        return path, suitable for carrying the maximum value of   Important requirements
        unbalanced flux without saturation. This is achieved by   Grounding  Based on the above, it is essential that
        the use of a five-limb transformer (Figure 15.4(b)). The   the primary windings of the transformer have a grounded
        two additional outer limb are left unwound.      neutral, without which no zero sequence exciting current
                                                         will flow through the primary windings. Although the
         2  Residual voltages under different operating condi-   open delta will develop some voltage on an unbalance
         tions  To extend the ease of application of this device,   in  the  primary,  it  will  only  be  the  third  harmonic
         consider the  following circuit  conditions to  determine   component,  as  would  be  contained  by  the  primary
         the quantum of residual voltages:               windings'  magnetic flux  and  not  the  zero  sequence
                                                         component.
                                                         Voltage factor  Since this transformer  may have to
          Healthy system: System neutral, grounded or ungroun-   perform  under  severe  fault  conditions,  it  should be
          ded.                                           suitable for sustaining system switching surges as well
          Ground fault on one phasc                      as  surges  developed  on  a  fault. A  voltage  factor as
          - System neutral grounded                      high  as  1.9  (Table  15.4) is  generally  prescribed  for
          - System neutral isolated                      these transformers.
   483   484   485   486   487   488   489   490   491   492   493