Page 490 - Industrial Power Engineering and Applications Handbook
        P. 490
     15/464  Industrial Power Engineering and Applications Handbook
          Short-time duty  When this transformer is required   which  is  reasonably  low compared to the high  system
          to  discharge  a  charged  capacitor bank  it  should  be   voltage. This helps restrict the phase error, on the one
          capable of withstanding heavy inrush discharge currents   hand, and facilitates an economical intermediate wound
          (see below for its application). The following may be   transformer T,, on the other, to perform the same duty as
          considered when designing a transformer for dischar-   a  normal  wound  voltage  transformer.  The purpose  of
          ging purposes:                               line capacitors is thus to step down the high to very high
          1  The size of  the capacitor banks, their voltage and   system voltages to an economically low value. Through
            the impedance of the capacitor circuit.    the tapping  point A is connected a conventional  and  a
          2  Rate of discharge of the trapped charge.   less  expensive  wound-type  intermediate  or  auxiliary
          3  The temperature of the primary windings after the   voltage transformer T,, rated for the intermediate voltage
             discharge.                                VI in association with a reactor L (Figure 15.6(b)). The
          4  The  magnitude  of  electrodynamic  forces  on  the   use of the reactor is to almost offset the heavy capacitive
            primary windings, which may be developed by the   voltage  component.  If  possible,  the  reactor  and  the
             discharge currents.                       transformer  may  be  combined  in  one  unit  to  make  it
          Applications  They  may  be  used  to  carry  out  the   easier to  operate. The secondary  of  the transformer  is
          following functions:                         rated for the required standard voltage, say, 110/ <3  (63.5
          1  To  detect  a ground  fault  or operate a directional   V), to feed the auxiliary devices and components fitted
             ground fault relay (Section 21.7.4).      in the auxiliary circuit.
          2  To operate  a neutral  displacement  relay  (Figures   The inductive reactance of the combined transformer
             26.4 and 26.9).                           and  the  reactor  is  chosen  so  that  it  will  balance  the
          3  To detect an unbalance in  a three-phase normally   capacitive reactance of  the line capacitors  at the rated
             balanced capacitor bank (Section 26.1.1(8)).   frequency and thus achieve a near-resonant circuit. Since
          4  To discharge a charged capacitor bank over a very   a frequency variation may cause a de-tuning of the resonant
             short  period,  particularly  when  a  fully  charged   circuit, tappings are generally provided on the intermediate
             capacitor is interrupted. See also Section 25.7.   voltage transformer to facilitate adjustment of the circuit
          5  To discharge an interrupted HT circuit before a re-   reactance  at  different  frequencies,  to  achieve  a  near-
             closing. An HT system, say, a transmission line or   resonant condition even on other frequencies. There is a
             a cable when  interrupted, develops high transient   voltage drop across both the capacitor units  Vc and the
             voltages as discussed in Sections 23.5.1 and 20.1.   reactor  VL. Figure  15.7 illustrates  a  simple equivalent
             Unless these transients are damped to a reasonably   circuit for the CVT of  Figure  15.6(b) for more clarity.
             low level so that they are not able to endanger the   These  voltage  drops,  being  180" out  of  phase,  are
             connected devices on an automatic reclosing, the   detrimental in influencing and adding to the phase error
             devices installed in the system may become damaged   of  the  intermediate  voltage  transformer  T,.  At higher
             due to the resulting switching transients. The normal   frequencies, the summation of these voltages  (V, + V,)
             practice to deal with this is to damp the transients   may become very high and cause high phase errors, leading
             through an electromagnetic transformer such as this.   to  erratic  behaviour  of  the  instruments,  devices and
             The transformer, however, may have to be designed   components  connected  on  the  secondary  of  the
             for such a duty to sustain the electrostatic stresses   intermediate voltage transformer. It is therefore, imperative
             arising from such transients, the discharge time and   that these voltage drops be contained as low as pgssibk,
             impedance  of  the  interrupting  circuit  up  to  the   on the one hand, and must offset each other, i.e.  Vc + V,
             transformer.                              = 0, on the other,  to remain  almost ineffective even at
                                                       higher frequency variations, in influencing the phase error
         15.4.4 Capacitor voltage transformers (CVTs)   of the intermediate VT.
                                                         Frequency variations are usually caused on a fault or
         This type of voltage transformer is normally meant for a   a  switching  operation  (Sections 20.1  and  23.5.1)  and
         high to an ultra-high  voltage  system, say,  110 kV  and   also  during  the  changeover  of  the  tapping  of  the
         above.  While  a  conventional  wound-type  (electro-   intermediate VT or the reactor. When the voltage drops
         magnetic)  voltage transformer  will  always be  the first   Vc and  VL  are  not  large  enough  compared  to  VI,  the
         choice, it may become costlier and highly uneconomical   content  of  phase  error  is  contained.  An  intermediate
         at such voltages.                             voltage of  almost  12-24  kV  is found to be realistic in
          The size  and therefore  the  cost  of  a conventionally   restricting the voltage drops across C and L, to a reasonably
         wound voltage transformer will  be almost proportional   low value compared to V, during normal operation. Further,
         to the system voltage for which it is wound. As a cost   it is essential to offset the reactances Xc and X, through
         consideration, therefore, a more economical alternative   a variable reactor to achieve a near-resonant circuit when
         is found in a Capacitor Voltage Transformer (CVT) (Figure   the  CVT is  in  service.  This  makes  the  whole  system
         15.6(a)).                                     behave like a normally wound VT in terms of  its rating
          A CVT consists of a capacitor divider unit in which a   and class of  accuracy for both  metering and protection
         primary  capacitor C,  and a secondary capacitor C2 are   purposes. The same error limits will apply as for a normal
         connected in  parallel between  the line and the ground   VT (Tables 15.5 and 15.6). The output for a given accuracy
         (Figure 15.6(b)). A tapping at point A is provided at an   is dependent on  the range  of  frequency  variation over
         intermediate  voltage  VI, usually  around  12  to  24  kV,   which the voltage transformer is required to operate.





