Page 486 - Industrial Power Engineering and Applications Handbook
P. 486

15/460  Industrial Power Engineering and Applications Handbook





                                                                                      Vl










                  6 = Phasor displacement error
                  Note  The phasor diagram is drawn taking the applied voltage VI  as the reference phasor. It can also be drawn
                  taking the primary induced emf  V,'  as the reference. The logic to the diagram and the subsequent results shall
                  however, remain the same.
                                  Figure 15.2  Phasor diagram for a voltage transformer



        Table 15.4  Rated voltage factors
        Sr: no.   Rated  voltage factor   Rated  time   Method  .f system grounding   Method  of primary connections
        ~~   ~   ~                                       ~-         -.  ~~
        1         1.2             Continuous    All  types of  system grounding   (i)  Between lines or
                                                                            (ii)  Between transformer
                                                                               star point and ground
        2         1.2             Continuous    An  effectively  grounded system   Between  line and ground
        3         1.5             30 seconds    An effectively  grounded  system   Between line and ground
        4         1.2             Continuous    An ineffectively  grounded  system   Between line and ground
        5         1.9             30 seconds    An  ineffectively  grounded  system   Between line and ground
        6         1.2             Continuous    (i)  An  isolated neutral system or   Between line and ground
                                                (ii)  A resonant grounded system
        7         1.9             8 hours       A resonant grounded system   Between  line and ground
                                                   ~
        Table  15.5  Recommended limits  of  voltage  and  phase   space, they may also be wound for one common primary
        displacement errors, applicable for  all types  of  measuring VTs   and two secondary windings, one for metering and the
        (only electromagnetic and capacitor VTs).      other for protection. For markings, see Section 15.10.1(2)
        (A residual VT is basically a protection VT)
                                                       and Figure 15.35.
        Class of  accuracy   6 voltage (ratio)  Phase displacement (6)
                       error fa     _+ minutey         15.4.3 Residual voltage transformers (RVTs)
                                   -~             ~
        0.1            0.1           5                 When  the  primary  of  a  three-phase  two-winding
        0.2            0.2          10                 transformer,  having  its  secondary  wound  for a  three-
        0.5            0.5          20                 phase open delta, is connected across an unbalanced supply
        1 .Q           1 .o         40                 system, a residual voltage across the open delta will appear.
        3.0            3.0          Not specified      This is the principle on which this transformer is based
                                                       (Figure  15.4(a)). As  discussed  in  Section  21.2.2,  and
        As in IEC-60044-2
                                                       illustrated in Figure 21.7, the phasor sum of all the three
        "These errors are valid only when the voltage is between 80% and   line to ground voltages in a three-phase balanced system
        120%, burden  25-1006  of the rated burden and p.f., 0.8 lagging.   is zero, i.e.
                                                       v, + v, + v, = 0
        Application
        They are used for both measuring and protection purposes.   When this balance is disturbed, due to either an unbalance
        As a measuring VT, they are used to feed a voltmeter,   in the loads or due to a ground fault, a residual or zero
        kW,  kWh or a kVAr  meter,  a  power  factor, frequency   phase sequence voltage in the neutral circuit will appear.
        meter or a  synchroscope. As a protection  VT they  are   When  one of  the  phases  in  the  secondary  of  a  three-
        used  to feed a protective  circuit, incorporating  voltage   phase  transformer  is  open  circuited  and  a  three-phase
        sensing protection relays. To save on cost and mounting   supply is applied to its primary windings, there will appear
   481   482   483   484   485   486   487   488   489   490   491