Page 485 - Industrial Power Engineering and Applications Handbook
        P. 485
     Instrument and control transformers: application and selection  15/459
        Note.$
         I  A  low Loltage  of  596,  at which  the transformer is required to
           maintain its accuracy limit, is of great significance. A protection
           transformer is required to operate under a fault condition, during
           which the primary  voltage  may dip to a value as low as 5% of
           the rated voltage.
        2   It is possible  to have two windings in the secondary circuit of
           a  VT when  it  is  required  to  perform  the  functions  of  both
           measurement and protection.
                                                        VI
         I1 Rated voltage factor
        This is the multiplying factor which, when applied to the
        rated  primary  voltage,  will  determine  the  maximum
         voltage at  which the transformer  will  comply with the   VI  - Primary voltage
        thermal requirements for a specified time as well as with   V,'  - Primary induced emf
        the relevant accuracy requirements. This factor carries a
        greater significance, particularly on a fault, when healthy   Vi - Secondary induced emf  referred to the primary side
        phases may experience an overvoltage and the protection   (V, being secondary induced emf  not shown)
        VTs  may  all  the  more be required  to accurately  sense   In(  - Excitation or no-load current
         this and activate the protective circuit. Such a situation   /,   - Loss component of current supplying the hysteresis and eddy
         may arise on a ground fault on an isolated neutral system   current losses to the voltage transformer core (it is the active
                                                           component)
         or  a  high  impedance grounded  system  (Section  20.6).   /,   - Magnetizing component producing the flux '0' (it is the reactive
        Table  15.4, following  IEC  60044-2,  suggests  the   component)
        recommended  voltage  factors  and  their  permissible   R,  - Primary circuit resistance
        durations for different grounding conditions.   Rg  - Secondary circuit  resistance referred to the primary side
                                                        X, - Primary circuit  reactance
         12 Circuit diagram                             X;  - Secondary circuit  reactance referred to the primary side
        To illustrate the important features of a VT, let us analyse   Z, - Primary circuit impedance
         its equivalent circuit diagram. Refer to a simple diagram   Zg  - Secondary circuit impedance referred to the primary side
         as in Figure  15.1 which is drawn along similar lines to   Z-  Load (burden) impedance
        those for a motor (Section  1.10, Figure  1.15). For ease   Figure 15.1  Equivalent circuit diagram for a voltage transformer
         of analysis, the ratio of primary and secondary turns has
         been  considered as  1 : I. Then from the circuit diagram,   14 Phase displacement errol; 6
         the following can be derived:                 This is the difference in phase between the primary and
                                                       the secondary voltage phasors (6). The direction of the
                                                       phasors are so chosen, that the angle is zero for a perfect
                                                       transformation. Refer to the phasor diagram, Figure 15.2,
                                                       and Table 15.5 for measuring and Table 15.6 for protection
         and this is drawn in the form of a phasor diagram (Figure   VTs  .
         15.2). The phase displacement between phasors   and
         Vi is the phase displacement error '6' as discussed later.   15 Limits  of  voltage and phase displacement errors
                                                         At rated frequency, these should not exceed the values
         13 Voltage error or ratio error                 given in Table 15.5 for measuring VTs. at any voltage
         This is the error in the transformed secondary voltage as   between  80% and  120%  of  the  rated  voltage  and  a
                                                         burden  of  25-100%  of  the rated  burden  at  a p.f.  0.8
         generally caused by the excitation current I,, and as shown
         in Figure 15.  1. It is the variation in the actual transforma-   lagging.
         tion  ratio from the rated and is expressed by   For protection VTs these should not exceed the values
                                                         given in Table 15.6 at any voltage between 5%  of the
                                                         rated, up to the voltages obtained by  multiplying the
                      K,  V,*  - V,*                     rated  voltage by  the rated  voltage factor as in Table
         Voltage error =         x  100%
                                                         15.4, and  a  burden  between  25%  and  100% of  the
                                                         rated load at a p.f. 0.8 lagging. At voltages lower than
         where                                           5%  of  the  rated,  the  limits  of  error  may  increase
         K, = rated transformation ratio                 disproportionately and become up to twice the specified
         VI = actual primary voltage (r.m.s.)            errors at about 2% of  the rated voltage. the limits of
         V, = actual secondary voltage (r.m.s.)          VA burden and p.f. remaining the same.
         NO I e                                        15.4.2 Electromagnetic voltage Transformers
         *Only the r.rn.s. values and not the phasor quantities are considered
         to define the voltage  error. The phase error is defined separately.   These  are  single-,  double-  or three-phase  wound-type
         Together they  form  the composite error.  Refer  to Table  15.5 for   trans-formers  with  windings  on  both  primary  and
         rneawring  and Table  15.6 for protection  VTs.   secondary sides (Figures  15.3(a) and (b)).





