Page 492 - Industrial Power Engineering and Applications Handbook
P. 492

15/466  Industrial Power Engineering and Applications  Handbook






                                               Z
       V1/d3
                                               R



       During resonance, when:
       X,  = X,  the circuit would behave like a normal transformer
        V,  : Voltage drop across the line capacitors
        V, : Voltage drop across the inductance
        Rl  : Primary resistance representing losses across '@ and 'L' and
           the intermediate voltage transformer (EMU)
        R;: Secondary resistance of the intermediate VT  referred to the   ts          bn
           primary side.
                                                      Figure 15.9  A typical outdoor type oil-filled  11 kV control
        /A  : Loss component                          transformer
        Irn  : Magnetizing component
        Z: Load (burden) impedance                    switchgear or a controlgear assembly not supposed to be
        R : Damping resistor to prevent ferro-resonance effects
                                                      connected directly to the main supply. These transformers
                                                      do not require a high accuracy and can be specified by
            Figure 15.7  Equivalent circuit diagram of  a CVT
                                                      the following parameters:
                                                        Rated primary voltage  The normal practice for an
       2  To feed the synchronizing equipment.          HT system is to provide a separate LT feeder for the
       3  As a coupling unit for carrier signals (Section 23.5.2   auxiliary  supplies. The primary  voltage  will be  the
         and Figure 23.9(b)).                           normal system voltage,  V,., when the transformer is
       4  To damp the transient voltages on the primary side.   connected line to line or  Vr1a when connected line
                                                        to neutral.
       For markings refer to Section 15.10.1 and Figure 15.35.   Rated secondary voltage  This is 24,48, 11 0, 220,
                                                        230, 240 or 250 volts, or according to the practice of
       15.4.5  Control transformers                     a country. Tappings, if required, can be provided on
                                                        the primary side.
       Refer to Figures  15.8 and  15.9. These transformers are   Rated burden  This  is the  maximum  burden  the
       quite  different  from  a  measuring  or  a  protection   transformer may have to feed at a time. The preferred
       transformer, particularly in terms of accuracy and short-   ratings  will  follow  series  R-10  of  ISO-3  (Section
       time VA ratings. They are installed to feed power to the   13.4.1(4)).
       control  or  the  auxiliary  deviceslcomponents  of  a   Short-time  VA  burden  This  accounts  for  the























                           Figure 15.8  Typical single-phase  and three-phase  control transformers
   487   488   489   490   491   492   493   494   495   496   497